Eaton Moeller series xEffect - AZ MCB. Miniature circuit breaker (MCB) AZ, 3 pole+N, Tripping characteristic: C, Rated current In: 63 A
Product Name |
Eaton Moeller series xEffect - AZ MCB
|
Catalog Number |
211798
|
EAN |
4015082117986
|
Product Length/Depth |
90 mm
|
Product Height |
75 mm
|
Product Width |
108 mm
|
Product Weight |
0.856 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC/EN 60947-2
EN45545-2 IEC 61373 |
Model Code |
AZ-3N-C63
|
Application |
|
Number of poles |
Three-pole + N
|
Number of poles (total) |
4
|
Number of poles (protected) |
3
|
Tripping characteristic |
C
|
Release characteristic |
C
|
Amperage Rating |
63 A
|
Type |
|
Voltage type |
AC
|
Voltage rating |
230 V AC / 400 V AC
|
Voltage rating at DC |
60 V DC (per pole)
|
Rated operational voltage (Ue) - max |
400 V
|
Rated insulation voltage (Ui) |
440 V
|
Rated impulse withstand voltage (Uimp) |
4 kV
|
Frequency rating - min |
50 Hz
|
Frequency rating - max |
60 Hz
|
Rated switching capacity (IEC/EN 60947-2) |
25 kA
|
Operational switching capacity |
20 kA
|
Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V |
0 kA
|
Rated short-circuit breaking capacity (IEC/EN 60898-1)- Icn at 400 V |
0 kA
|
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V |
25 kA
|
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V |
25 kA
|
Admissible back-up fuse - max |
200 A gL/gG
|
Selectivity class |
3
|
Overvoltage category |
III
|
Pollution degree |
2
|
Lifespan, electrical |
10000 operations
|
Direction of incoming supply |
As required
|
Frame |
45 mm
|
Enclosure width |
90 mm
|
Width in number of modular spacings |
6
|
Built-in depth |
75 mm
|
Mounting width per pole |
27 mm
|
Mounting width |
27 mm
|
Degree of protection |
IP40 (when fitted)
IP20 |
Terminals (top and bottom) |
Lift terminals
|
Connectable conductor cross section (solid-core) - min |
2.5 mm²
|
Connectable conductor cross section (solid-core) - max |
50 mm²
|
Connectable conductor cross section (multi-wired) - min |
2.5 mm²
|
Connectable conductor cross section (multi-wired) - max |
50 mm²
|
Terminal capacity (control cable) |
2.5 mm² - 50 mm²
|
Terminal protection |
Finger and hand touch safe, DGUV VS3, EN 50274
|
Rated operational current for specified heat dissipation (In) |
63 A
|
Heat dissipation per pole, current-dependent |
5.2 W
|