Nuotrauka reprezentatyvi
Download
Eaton Moeller® series AING Power supply unit, 1p, 192VA, prim 230VAC, sec. 24VAC, 24 V DC, 10 V DC
| Product Name |
Eaton Moeller® series AING Power supply unit
|
| Catalog Number |
269517
|
| EAN |
4015082695170
|
| Product Length/Depth |
90 mm
|
| Product Height |
155 mm
|
| Product Width |
110 mm
|
| Product Weight |
3.9 kg
|
| Certifications |
Safety transformer to IEC/EN 61558-2-2/2-6
VDE 0113 VDE 0570 Part 2-2/2-6 (safety transformer) IEC/EN 60204-1 |
| Catalog Notes |
Non-standard voltages on request
|
| Model Code |
AING8
|
| Features |
Fully Vacuum-impregnated
Separate windings Reinforced insulation |
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Degree of Protection |
IP20
|
| Output voltage at DC - min |
24 V
|
| Rated frequency - max |
60 Hz
|
| Rated frequency - min |
50 Hz
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Rated power |
0.192 VA
|
| Static heat dissipation, non-current-dependent Pvs |
50 W
|
| Product category |
Universal power supply unit AING
|
| Duty factor |
100 %
|
| Power output |
192 W
|
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Input current at AC - max |
0.83 A
|
| Input current at DC - max |
0 A
|
| Input voltage at AC 50 Hz - max |
230 V
|
| Input voltage at AC 50 Hz - min |
230 V
|
| Input voltage at AC 60 Hz - max |
230 V
|
| Input voltage at AC 60 Hz - min |
230 V
|
| Input voltage at DC - max |
0 V
|
| Input voltage at DC - min |
0 V
|
| Insulation class |
B
|
| Suitable for |
Safety functions
|
| Primary tapping |
± 5 %
|
| Connection type |
Terminations
|
| Output current at AC, 50 Hz - max |
8 A
|
| Output current at AC, 60 Hz - max |
8 A
|
| Output current at DC - max |
3 A
|
| Output voltage at AC 50 Hz - max |
24 V
|
| Output voltage at AC 50 Hz - min |
24 V
|
| Output voltage at AC 60 Hz - max |
24 V
|
| Output voltage at AC 60 Hz - min |
24 V
|
| Output voltage at DC - max |
24 V
|