Atsisiųsti dokumentą () iš 20

PV-10A10F

Eaton Bussmann series photovoltaic fuses, 1000 Vdc, 10A, 50 kAIC, Non Indicating, IEC 60269-6 type A, Class gPV, Time constant: 1-3 ms, Ferrule end x ferrule end

General specifications

Product Name
Eaton Bussmann series photovoltaic fuses
Catalog Number
PV-10A10F
EAN
5027590505352
UPC
051712204019
Product Length/Depth
38 mm
Product Height
10 mm
Product Width
10 mm
Product Weight
9.4 g
Compliances
RoHS Compliant
CE Marked
Certifications
CSA Certified
IEC Rated
UL Listed
UL 2579
UL approval pending
CCC Marked

Gaminio specifikacijos

Used with
BM Series, CHPV, 1A3400 fuseclips, HPV
Amperage Rating
10 A
Accessories
CHPV1IU. CHPV1U, CHPV2IU, CHPV2U, 1A3400-_, HPV-DV-_A, 1A3400 fuse clip
Breaking capacity
50 kA
With striker
No
Voltage type
DC
Utilization category
gPV (photovoltaic protection)
Release characteristic
Other
Fuse indicator
Other
Rated switching capacity
50 kA
Fuse size
10 x 38 mm
Current type
DC
Rated voltage DC
1000 V
Class
Class gPV
Watt losses
1.2 W
Fuse shape
Cylindrical
Pre arc (I2T)
7
Terminal material
Tin plated brass
Total I2T
70 at 1000 V
Color
White
Interrupt rating
50 kAIC
Connection
Ferrule end x ferrule end
Construction size
10 x 38 mm
Material
Ceramic
Mounting method
Holder
Quantity
10
Voltage rating
1000 Vdc
Type
Cylindrical
Special features
Minimum interrupting rating 1.3 x In, Time constant: 1-3 ms
Application
Combiner boxes, inverters, pv wire harnesses, Photovoltaic strings
Fuse type
PV-A10F
Suitable for
CHPV Modular fuse holder
HPV-DV Inline holder
Breaking capacity at nominal voltage, DC
50 kA

Eksportuoti gaminio specifikaciją

Pastaba: Jei failo atsisiųstame .zip pakete nėra, vadinasi šio tipo failas nėra tinkamas atsisiųsti kartu su kitais.