Eaton Moeller® series R9 Switch-disconnector, R9, UL98, 100 A, rear mounting, 3 pole, Without rotary handle and drive shaft
| Product Name |
Eaton Moeller® series R9 Switch-disconnector
|
| Catalog Number |
191855
|
| EAN |
4015081923762
|
| Product Length/Depth |
81 mm
|
| Product Height |
132 mm
|
| Product Width |
78 mm
|
| Product Weight |
0.55 kg
|
| Certifications |
UL
VDE 0660 CSA IEC/EN 60947 |
| Catalog Notes |
Without rotary handle and drive shaft
|
| Model Code |
R9C3100U
|
| Product Category |
|
| Features |
Version as main switch
Version as emergency stop installation Version as maintenance-/service switch |
| Actuator color |
Other
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
UV resistance only in connection with protective shield.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Rated impulse withstand voltage (Uimp) |
8000 V AC
|
| Rated permanent current at AC-21, 400 V |
0 A
|
| Rated permanent current at AC-23, 400 V |
81 A
|
| Rated uninterrupted current (Iu) |
100 A
|
| Switching power at 400 V |
0 kW
|
| Accessories |
Auxiliary contact or neutral conductor fitted by user.
|
| Device construction |
Built-in device fixed built-in technique
|
| Rated short-time withstand current (Icw) |
0 kA
|
| Electrical connection type of main circuit |
Frame clamp
|
| Mounting position |
As required
|
| Actuator type |
Other
|
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Rated conditional short-circuit current (Iq) |
0 kA
|
| Control circuit reliability |
1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
|
| Degree of protection (front side) |
IP20
|
| Number of poles |
Three-pole
|
| Mounting method |
Rear mounting
|
| Degree of protection |
NEMA Other
|
| Suitable for |
Intermediate mounting
Ground mounting |
| Functions |
Optional Stop Function
Interlockable |
| Number of switches |
1
|
| Screw size |
4 mm AF, Hexagon socket-head spanner, Terminal screw
|
| Switching capacity (auxiliary contacts, general use) |
10A, IU, (UL/CSA)
|
| Switching capacity (auxiliary contacts, pilot duty) |
A300 (UL/CSA)
|
| Terminal capacity |
6 - 70 mm²
10 - 2/0 AWG |
| Switching capacity (main contacts, general use) |
100 A, Rated uninterrupted current max. (UL/CSA)
|
| Safety parameter (EN ISO 13849-1) |
B10d values as per EN ISO 13849-1, table C.1
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Rated operating voltage (Ue) - max |
690 V
|
| Rated operating voltage (Ue) - min |
690 V
|
| Rated operational voltage (Ue) at AC - max |
690 V
|
| Short-circuit current rating (high fault) |
100 kA, 480 V, SCCR (UL/CSA)
25 kA, 600 V, SCCR (UL/CSA) 100 A, Class J, max. Fuse, SCCR (UL/CSA) |
| Rated operational power at AC-23A, 400 V, 50 Hz |
45 kW
|
| Rated operational power at AC-23A, 500 V, 50 Hz |
45 kW
|
| Rated operational power at AC-23A, 690 V, 50 Hz |
45 kW
|
| Rated operational power at AC-3, 380/400 V, 50 Hz |
0 kW
|
| Tightening torque |
3.5 Nm, 6 mm², Screw terminals
31 lb-in, 10 AWG , Screw terminals 35.4 lb-in, 8 - 2 AWG , Screw terminals 44.3 lb-in, 1 - 2/0 AWG , Screw terminals 5 Nm, 50 - 70 mm², Screw terminals 4 Nm, 10 - 35 mm², Screw terminals |
| Uninterrupted current |
Rated uninterrupted current Iu is specified for max. cross-section.
|
| Housing material |
Plastic
|