Bilgi Arama
Belgeyi İndir () / 20
Zor İşler Bizimle Kolay

263582
Model Kodu: PF7-63/2/01-DE

Eaton Moeller series xPole - PF6/7 RCCB. PF7, 2 pole, In: 63 A, Icn: 10 kA, IΔN: 0.1 A, Type AC, AC current sensitive, Partly surge-proof 250 A, residential and commercial

General specifications

Product Name
Eaton Moeller series xPole - PF6/7 RCCB
Catalog Number
263582
EAN
4015082635824
Product Length/Depth
76 mm
Product Height
80 mm
Product Width
35 mm
Product Weight
0.22 kg
Compliances
RoHS conform
Certifications
IEC/EN 61008
Model Code
PF7-63/2/01-DE

Additional information

Accessories required
Z-HK 248432
Features
Additional equipment possible
Residual current circuit breaker
Fitted with:
IS/SPE-1TE 101911
Interlocking device
Special features
  • Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.8% for every 1 °C
  • Tripping signal contact for subsequent installation Z-NHK 248434
Used with
KLV-TC-2 276240 (Compact enclosure)
Z-FW/LP 248296 (Remote control and automatic switching device)
Z-RC/AK-2TE 285385 (sealing cover set)

Delivery program

Amperage Rating
63 A
Application
  • Residual current circuit breaker for residential and commercial applications
  • xPole - Switchgear for residential and commercial applications
Fault current rating
100 mA
Impulse withstand current
Partly surge-proof 250 A
Number of poles
Two-pole
Rated short-circuit strength
10 kA
Sensitivity type
AC current sensitive
Tripping time
Non-delayed
Type
  • PF7
  • Residual current circuit breakers
  • Type AC

Design verification as per IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature - max
60 °C
Ambient operating temperature - min
-25 °C
Equipment heat dissipation, current-dependent
7.2 W
Heat dissipation capacity
0 W
Heat dissipation per pole, current-dependent
0 W
Rated operational current for specified heat dissipation (In)
63 A
Static heat dissipation, non-current-dependent
0 W

Technical Data - Electrical

Admissible back-up fuse overload - max
40 A gG/gL
Frequency rating
50 Hz
Leakage current type
AC
Lifespan, electrical
4000 operations
Pollution degree
2
Rated fault current - max
0.1 A
Rated fault current - min
0.1 A
Rated impulse withstand voltage (Uimp)
4 kV
Rated insulation voltage (Ui)
440 V
Rated operational voltage (Ue) - max
230 V
Rated residual making and breaking capacity
630 A
Rated short-time withstand current (Icw)
10 kA
Short-circuit rating
63 A (max. admissible back-up fuse)
Surge current capacity
0.25 kA
Test circuit range
184 V AC - 250 V AC
Voltage rating
230 V AC

Technical Data - Mechanical

Built-in depth
69.5 mm
Built-in width (number of units)
35 mm (2 SU)
Busbar material thickness
0.8 mm - 2 mm
Climatic proofing
25-55 °C / 90-95% relative humidity according to IEC 60068-2
Connectable conductor cross section (multi-wired) - max
16 mm²
Connectable conductor cross section (multi-wired) - min
1.5 mm²
Connectable conductor cross section (solid-core) - max
35 mm²
Connectable conductor cross section (solid-core) - min
1.5 mm²
Degree of protection
IP20, IP40 with suitable enclosure
IP20
Frame
45 mm
Lifespan, mechanical
20000 operations
Mounting Method
DIN rail
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Permitted storage and transport temperature - max
60 °C
Permitted storage and transport temperature - min
-35 °C
Terminal capacity (solid wire)
1.5 mm² - 35 mm²
Terminal capacity (stranded cable)
16 mm² (2x)
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Terminals (top and bottom)
Open mouthed/lift terminals
Width in number of modular spacings
2

Ürün teknik özelliklerini aktar

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Ürünü Doğrula

16 veya 17 haneli seri numaranızı girin.
Girdiğiniz seri numarası özel karakter içermemelidir. Girdiğiniz seri numarası doğru değil, seri numarası 16 veya 17 haneli olmalıdır. Girdiğiniz seri numarası bulunamadı. Lütfen tekrar deneyin veya Bu sorunu bildir daha fazla destek için. Girdiğiniz seri numarası ürünle eşleşmiyor. Girdiğiniz seri numarası ürünle eşleşmiyor. Tıkla buraya Girdiğiniz seri numarasına ait ürün sayfasına gitmek için… Bu seri numarası Eaton tarafından şüpheli olarak tanımlanmıştır, lütfen tekrar deneyin veya… Bu sorunu bildir daha fazla destek için.
Seri numarası
Sıfırla Bu seri numarası Eaton tarafından şüpheli olarak tanımlanmıştır, lütfen tekrar deneyin veya… Bu sorunu bildir daha fazla destek için. Bu seri numarası Eaton tarafından tanınmıyor ve geçersiz. Lútfen bu formu kullanın Bu sorunu bildir daha fazla destek için.
6 haneli doğrulama kodunu girin.
Girdiğiniz ürün şüpheli görünüyor! Lütfen tekrar deneyin veya Bu sorunu bildir daha fazla destek için. Girdiğiniz doğrulama kodu bu seri numarası için kayıtlarımızla eşleşmiyor. Lütfen tekrar deneyin veya Bu sorunu bildir daha fazla destek için. Geçersiz Doğrulama kodu. Doğrulama kodu 6 haneden oluşmalıdır. Bu sorunu bildir daha fazla destek için. Doğrulama kodu gereklidir Bu sorunu bildir daha fazla destek için.
Doğrulama işleminden önce, Captcha güvenlik doğrulamasını tamamlayın.
Bize Ulaşın Bir sorunu bildirmek için
x
Sorun Bildirin
Lütfen tam adınızı girin.
x
Teşekkür ederiz, talebiniz alındı. Ürün ekibimiz sizinle kısa süre içinde iletişime geçecek.
Not: .zip indirmesinde dosya(lar) eksikse dosya türü toplu indirme tarafından desteklenmiyor demektir.