Eaton Moeller series Power Defense molded case circuit-breaker, 200A, 50kA, 4p, screw terminal
Product Name |
Eaton Moeller series Power Defense molded case circuit-breaker
|
Catalog Number |
PDE26K0200TAAS
|
EAN |
9008790969980
|
Product Length/Depth |
201 mm
|
Product Height |
89 mm
|
Product Width |
140 mm
|
Product Weight |
2.268 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
IEC/EN 60947 |
Model Code |
PDE26K0200TAAS
|
Amperage Rating |
200 A
|
Voltage rating |
220 V - 440 V
|
Circuit breaker frame type |
PDE2
|
Features |
Protection unit
Motor drive optional |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
3
|
Mounting Method |
DIN rail (top hat rail) mounting optional
Complete device in housing Fixed |
Utilization category |
A
|
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-20 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-20 °C
|
Rated current (Iu) |
200 A
|
Max. rated operation voltage Ue AC |
440
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Degree of protection |
IP2X
|
Direction of incoming supply |
Vertical and 90° in all directions
|
Electrical connection type of main circuit |
Screw connection
|
Lifespan, mechanical |
20000 operations
|
Overvoltage category |
III
|
Number of poles |
Four-pole
|
Functions |
System and cable protection
|
Type |
Circuit breaker
|
Special features |
Thermally and magnetically adjustable (calibrated at 40 °C)
|
Position of connection for main current circuit |
Front side
|
Power loss |
58 W
|
Release system |
Thermomagnetic release
|
Handle type |
Rocker lever
|
Short delay current setting (Isd) - max |
0 A
|
Short delay current setting (Isd) - min |
0 A
|
Instantaneous current setting (Ii) - max |
1600 A
|
Instantaneous current setting (Ii) - min |
1000 A
|
Number of operations per hour - max |
120
|
Overload current setting (Ir) - max |
200 A
|
Overload current setting (Ir) - min |
160 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
65 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
50 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
26 kA
|
Standard terminals |
Screw terminal
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
4000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
8000 V
|
Voltage rating (DC) |
250 V
|
Rated insulation voltage (Ui) |
800 V AC
|