Reset
Eaton Moeller series Power Defense - Molded Case Circuit Breaker. Circuit breaker, 630A, 70kA/50kA, 4p/6, screw terminal, frame 3
| Product Name |
Eaton Moeller series Power Defense molded case circuit-breaker
|
| Catalog Number |
PDE36M0630TAAS
|
| EAN |
9010238103955
|
| Product Length/Depth |
257 mm
|
| Product Height |
138 mm
|
| Product Width |
183 mm
|
| Product Weight |
7 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC
IEC/EN 60947 |
| Model Code |
PDE36M0630TAAS
|
| Type |
Circuit breaker
|
| Circuit breaker frame type |
PDE3
|
| Number of poles |
Three-pole
|
| Amperage Rating |
630 A
|
| Release system |
Thermomagnetic release
|
| Features |
Protection unit
Motor drive optional |
| Special features |
Thermally and magnetically adjustable (calibrated at 40 °C)
|
| Voltage rating |
220 V - 440 V
|
| Voltage rating (DC) |
250 V
|
| Rated impulse withstand voltage (Uimp) at auxiliary contacts |
4000 V
|
| Rated impulse withstand voltage (Uimp) at main contacts |
8000 V
|
| Rated current (Iu) |
630 A
|
| Amperage Rating |
630 A
|
| Instantaneous current setting (Ii) - min |
3150 A
|
| Instantaneous current setting (Ii) - max |
5040 A
|
| Overload current setting (Ir) - min |
504 A
|
| Overload current setting (Ir) - max |
630 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
100 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
70 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
37 kA
|
| Electrical connection type of main circuit |
Screw connection
|
| Number of operations per hour - max |
60
|
| Handle type |
Rocker lever
|
| Utilization category |
A
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Direction of incoming supply |
Vertical and 90° in all directions
|
| Mounting Method |
Complete device in housing
Fixed DIN rail (top hat rail) mounting optional |
| Mounting Method |
Complete device in housing
Fixed DIN rail (top hat rail) mounting optional |
| Degree of protection |
IP2X
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Position of connection for main current circuit |
Front side
|
| Special features |
Thermally and magnetically adjustable (calibrated at 40 °C)
|
| Lifespan, mechanical |
15000 operations
|
| Standard terminals |
Screw terminal
|
| Ambient operating temperature - min |
-20 °C
|
| Ambient operating temperature - max |
70 °C
|
| Ambient storage temperature - min |
-20 °C
|
| Ambient storage temperature - max |
70 °C
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| Functions |
System and cable protection
|