Eaton DC1 Variable frequency drive, 230 V AC, 1-phase, 10.5 A, 1.1 kW, IP66/NEMA 4X, Radio interference suppression filter, Brake chopper, 7-digital display assembly, Additional PCB protection, UV resistant, FS2
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
199391
|
EAN |
4015081977802
|
Product Length/Depth |
182 mm
|
Product Height |
257 mm
|
Product Width |
188 mm
|
Product Weight |
3.5 kg
|
Certifications |
UL File No.: E172143
IEC/EN 61800-5-1 EAC UL Listed UL 508C UL Category Control No.: NMMS, NMMS7 IEC/EN 61800-3 Certified by UL for use in Canada UL report applies to both US and Canada CE RCM CUL IEC/EN61800-5 RoHS, ISO 9001 CE marking UL UkrSEPRO IEC/EN 61800-2 CSA-C22.2 No. 14 |
Model Code |
DC1-S2011FB-A66OE1
|
Features |
Parameterization: drivesConnect
Parameterization: Fieldbus Parameterization: drivesConnect mobile (App) Parameterization: Keypad |
Fitted with: |
Brake chopper
Radio interference suppression filter IGBT inverter Internal DC link UV resistance Control unit 7-digital display assembly Additional PCB protection Breaking resistance PC connection |
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
No
|
Operating mode |
Speed control with slip compensation
BLDC motors U/f control Synchronous reluctance motors PM motors Sensorless vector control (SLV) |
Frame size |
FS2
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-20 °C
|
Mains voltage - max |
240 V
|
Output voltage - max |
250 V
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Ambient storage temperature - max |
60 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 230 V |
2.42 kVA
|
Apparent power at 240 V |
2.52 kVA
|
Application in industrial area permitted |
Yes
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Switch-on threshold for the braking transistor |
390 VDC
|
Voltage rating - max |
240 V
|
Mounting position |
Vertical
|
Communication interface |
CANopen®, built in
OP-Bus (RS485), built in Modbus RTU, built in SmartWire-DT, optional |
Converter type |
U converter
|
Degree of protection |
IP66
NEMA 4X |
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
1.5 HP
|
Braking resistance |
100 Ω
|
Input current ILN at 150% overload |
14 A
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
9.6 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
10.5 A
|
Protocol |
EtherNet/IP
CAN MODBUS Other bus systems |
Overload current IL at 150% overload |
15.75 A
|
Rated frequency - max |
62 Hz
|
Rated frequency - min |
48 Hz
|
Rated operational power at 220/230 V, 50 Hz, 1-phase |
1.1 kW
|
System configuration type |
AC supply systems with earthed center point
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit |
Cable length |
300 m, unscreened, with motor choke, maximum permissible, Motor feeder
C3 ≤ 25 m, maximum motor cable length C2 ≤ 5 m, maximum motor cable length 100 m, screened, maximum permissible cable length 200 m, screened, with motor choke, maximum permissible cable length 150 m, unscreened, maximum permissible cable length C1 ≤ 1 m, maximum motor cable length |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
230 V AC, single-phase
240 V AC, single-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
4
|
Radio interference class |
C1: for conducted emissions only
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Number of outputs (digital) |
1
|
Starting current - max |
175 % IH
|
Number of phases (input) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Number of phases (output) |
1
|
Power consumption |
103.4 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
97 % (η)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
2.49 mA
|
Mains voltage - min |
200 V
|
Nominal output current I2N |
11 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
1.1 kW
|
Output at quadratic load at rated output voltage - max |
1.1 kW
|
Output frequency - max |
500 Hz
|
Output frequency - min |
0 Hz
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
Rated operational current (Ie) |
10.5 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C)
|
Rated operational voltage |
230 V AC, 1-phase
240 V AC, 1-phase |
Short-circuit protection rating |
25 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|