Eaton Moeller® series DTZ Three-phase control isolating safety transformer, 10 kVA, Rated input voltage 50 – 950 ± 5 % V, Rated output voltage 18.5 – 1000 V
Product Name |
Eaton Moeller® series DTZ Control transformer
|
Catalog Number |
914812
|
Product Length/Depth |
216 mm
|
Product Height |
374 mm
|
Product Width |
390 mm
|
Product Weight |
70 kg
|
Certifications |
UL Category Control No.: XPTQ2, XPTQ8
IEC/EN 61558-2-2 CE |
Model Code |
DTZ10(*/*)*
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-25 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Primary voltage 1 - max |
950 V
|
Primary voltage 1 - min |
50 V
|
Primary voltage 10 - max |
0 V
|
Primary voltage 10 - min |
0 V
|
Primary voltage 2 - max |
950 V
|
Primary voltage 2 - min |
50 V
|
Primary voltage 3 - max |
950 V
|
Primary voltage 3 - min |
50 V
|
Primary voltage 4 - max |
950 V
|
Primary voltage 4 - min |
50 V
|
Primary voltage 5 - max |
950 V
|
Primary voltage 5 - min |
50 V
|
Primary voltage 6 - max |
950 V
|
Primary voltage 6 - min |
50 V
|
Primary voltage 7 - max |
0 V
|
Built as |
Isolating transformer
Safety transformer |
Conductor material |
Copper
|
Degree of protection |
IP00
NEMA Other |
Insulation material type (IEC 85) |
B
|
Primary voltage 7 - min |
0 V
|
Primary voltage 8 - max |
0 V
|
Primary voltage 8 - min |
0 V
|
Primary voltage 9 - max |
0 V
|
Primary voltage 9 - min |
0 V
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Rated power |
10000 VA
|
Secondary voltage 1 - max |
1000 V
|
Secondary voltage 1 - min |
18.5 V
|
Secondary voltage 10 - max |
0 V
|
Secondary voltage 10 - min |
0 V
|
Secondary voltage 2 - max |
1000 V
|
Secondary voltage 2 - min |
18.5 V
|
Secondary voltage 3 - max |
1000 V
|
Secondary voltage 3 - min |
18.5 V
|
Secondary voltage 4 - max |
1000 V
|
Secondary voltage 4 - min |
18.5 V
|
Secondary voltage 5 - max |
1000 V
|
Secondary voltage 5 - min |
18.5 V
|
Secondary voltage 6 - max |
1000 V
|
Secondary voltage 6 - min |
18.5 V
|
Secondary voltage 7 - max |
0 V
|
Secondary voltage 7 - min |
0 V
|
Secondary voltage 8 - max |
0 V
|
Secondary voltage 8 - min |
0 V
|
Secondary voltage 9 - max |
0 V
|
Secondary voltage 9 - min |
0 V
|
Short-time rating |
25 kVA
|
Static heat dissipation, non-current-dependent Pvs |
360 W
|
Voltage rating - max |
600 V
|
Product category |
Three-phase DTZ control transformers
|
Relative short-circuit voltage |
3.5 %
|
Suitable for |
Branch circuits, (UL/CSA)
|
Wiring system |
Other
|