Kunnskapssøk
Last ned dokumentet () av 20
We make what matters work*

192585
Modellkode: NZMH2-PMX200-NA

NZMH2-PMX200-NA. NZM2 PXR25 circuit breaker, 200A, 3p, Screw terminal, UL/CSA

General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
192585
EAN
4015081933136
Product Length/Depth
149 mm
Product Height
195 mm
Product Width
105 mm
Product Weight
2.345 kg
Compliances
RoHS conform
Certifications
IEC 60947-2
Specially designed for North America
UL (File No. E31593)
UL508
CSA (File No. 22086)
CSA-C22.2 No. 5-09
IEC
UL listed
UL/CSA
CSA (Class No. 1432-01)
CSA certified
IEC/EN 60947
UL (Category Control Number DIVQ)
CE marking
UL 489
Model Code
NZMH2-PMX200-NA

Ytterligere informasjon

Functions
Motor protection
Phase failure sensitive
Current limiting circuit breaker

Leveringsprogram

Amperage Rating
200 A
Application
Branch circuits, feeder circuits
Circuit breaker frame type
NZM2
Fitted with:
Thermal protection
Number of poles
Three-pole
Release system
Electronic release
Special features
  • Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit breaker (Rated short-circuit breaking capacity Icn)
  • Rated current = rated uninterrupted current: 200 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Type
Circuit breaker

Designverifisering etter IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Designverifisering etter IEC/EN 61439 – Tekniske data

Ambient operating temperature - max
70 °C
Ambient storage temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - min
40 °C
Equipment heat dissipation, current-dependent
33 W
Rated operational current for specified heat dissipation (In)
200 A

Technical data - electrical

Amperage Rating
200 A
Direction of incoming supply
As required
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever
Instantaneous current setting (Ii) - max
3000 A
Instantaneous current setting (Ii) - min
400 A
Isolation
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts)
Lifespan, electrical
6500 operations at 400 V AC-3
10000 operations at 400 V AC-1
5000 operations at 690 V AC-3
6500 operations at 415 V AC-3
7500 operations at 690 V AC-1
Number of operations per hour - max
120
Overload current setting (Ir) - max
220 A
Overload current setting (Ir) - min
88 A
Overvoltage category
III
Pollution degree
3
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated insulation voltage (Ui)
690 V
Rated operating power at AC-3, 230 V
55 kW
Rated operating power at AC-3, 400 V
110 kW
Rated operating voltage Ue (UL) - max
480 V
Rated operational current
300 A (690 V AC-1, making and breaking capacity)
300 A (400 V AC-1, making and breaking capacity)
250 A (660-690 V AC-3, making and breaking capacity)
300 A (415 V AC-1, making and breaking capacity)
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
150 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
130 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
130 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
37.5 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
5 kA
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
330 kA
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz
330 kA
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz
286 kA
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz
105 kA
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
40 kA
Rated short-time withstand current (t = 0.3 s)
1.9 kA
Rated short-time withstand current (t = 1 s)
1.9 kA
Short-circuit release non-delayed setting - max
3000 A
Short-circuit release non-delayed setting - min
400 A
Short-circuit total breaktime
< 10 ms
Utilization category
A (IEC/EN 60947-2)
Voltage rating
690 V - 690 V

Technical data - mechanical

Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Degree of protection
IP20
IP20 (basic degree of protection, in the operating controls area)
Degree of protection (IP), front side
IP40 (with insulating surround)
IP66 (with door coupling rotary handle)
Degree of protection (terminations)
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and strip terminal)
Lifespan, mechanical
20000 operations
Mounting Method
Built-in device fixed built-in technique
Fixed
Protection against direct contact
Finger and back-of-hand proof to VDE 0106 part 100
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Special features
  • Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit breaker (Rated short-circuit breaking capacity Icn)
  • Rated current = rated uninterrupted current: 200 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Switch off technique
Electronic

Technical data - mechanical - terminals

Standard terminals
Screw terminal
Terminal capacity (copper busbar)
M8 at rear-side screw connection
Terminal capacity (copper solid conductor/cable)
16 mm² (1x) at tunnel terminal

Eksporter produktspesifikasjoner

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autentiser produktet

Skriv inn ditt serienummer på 16-17 siffer
Serienummeret du oppgir kan ikke inneholde spesialtegn. Serienummeret du har oppgitt er feil, det må bestå av 16 eller 17 siffer. Finner ikke serienummeret du har oppgitt. Prøv på nytt eller rapporter dette problemet for å få hjelp. Serienummeret du har oppgitt samsvarer ikke med produktet. Kontroller produktets serienummer og prøv på nytt. Klikke her for å gå til produktsiden for serienummeret du har oppgitt Serienummeret er kjent for Eaton for å være mistenkelig, prøv på nytt eller rapporter dette problemet for å få hjelp.
Serienummer
Tilbakestill Serienummeret er kjent for Eaton for å være mistenkelig, prøv på nytt eller rapporter dette problemet for å få hjelp. Serienummeret gjenkjennes ikke av Eaton og er ugyldig. Bruk dette skjemaet for å rapporter dette problemet for å få hjelp.
Oppgi den sekssifrede autentiseringskoden
Produktet du har oppgitt er mistenkelig! Prøv på nytt eller rapporter dette problemet for å få hjelp. Autentiseringskoden du har oppgitt samsvarer ikke med våre registreringer for dette serienummeret. Prøv på nytt eller rapporter dette problemet for å få hjelp. Ugyldig autentiseringskode. Lengden må være seks tegn rapporter dette problemet for å få hjelp. Autentiseringskode kreves rapporter dette problemet for å få hjelp.
Fullfør Captcha-utfordringen før du autentiserer.
Kontakt oss for å rapportere problemet
x
Rapporter et problem
Oppgi fullt navn.
x
Takk, problemet er registrert og produktteamet vårt kontakter deg snart.
Merk: Hvis fil(er) mangler i .zip-nedlastingen, støttes ikke filtypen av bulknedlasting.