Belgeyi İndir () / 20

112884
Model Kodu: NZM3-XKV70KB

Eaton Moeller series NZM - Molded Case Circuit Breaker. Connection width extension, 3p, short

General specifications

Product Name
Eaton Moeller series NZM connection type
Catalog Number
112884
EAN
4015081124299
Product Length/Depth
255 mm
Product Height
36 mm
Product Width
200 mm
Product Weight
0.675 kg
Compliances
IEC
UL/CSA
RoHS conform
Certifications
UL489
IEC60947
CSA-C22.2 No. 5-09
CE marking
Request filed for UL and CSA
Model Code
NZM3-XKV70KB

Delivery program

Type
Accessory Connection width extension Terminal
Number of poles
Three-pole
Amperage Rating
630 A
Special features
One M12 threaded stud
Frame
NZM3
Suitable for
Copper cable lugs
Three-pole
Used with
NZM3, PN3, N(S)3

Technical Data - Electrical

Amperage Rating
630 A

Technical Data - Mechanical

Special features
One M12 threaded stud

Technical Data - Mechanical - Terminals

Terminal capacity (flexible cable)
500 AWG/kcmil (2x)
95 mm² - 300 mm² (2x)
Terminal capacity (copper busbar)
10 mm x 40 mm (2x)
Terminal capacity (copper strip)
10 segments of 32 mm x 1 mm (2x)

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.