Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 4p, 320A, withdrawable unit, H3-4-A320-SVE
Product Name |
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
|
Catalog Number |
168889
|
EAN |
4015081653812
|
Product Length/Depth |
335 mm
|
Product Height |
215.2 mm
|
Product Width |
185 mm
|
Product Weight |
8.81 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
|
Model Code |
NZMH3-4-A320-SVE
|
Voltage rating |
690 V - 690 V
|
Current rating of neutral conductor |
200% of phase conductor
|
Amperage Rating |
320 A
|
Instantaneous current setting (Ii) - min |
1920 A
|
Instantaneous current setting (Ii) - max |
19200 A
|
Overload current setting (Ir) |
250 A - 320 A
|
Overload current setting (Ir) - min |
250 A
|
Overload current setting (Ir) - max |
320 A
|
Short delay current setting (Isd) - min |
0 A
|
Short delay current setting (Isd) - max |
0 A
|
Short-circuit release non-delayed setting - min |
1920 A
|
Short-circuit release non-delayed setting - max |
3200 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 500 V DC |
70 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 750 V DC |
70 kA
|
Electrical connection type of main circuit |
Screw connection
|
Handle type |
Rocker lever
|
Current rating of neutral conductor |
200% of phase conductor
|
Amperage Rating |
320 A
|
Instantaneous current setting (Ii) - min |
1920 A
|
Instantaneous current setting (Ii) - max |
19200 A
|
Overload current setting (Ir) |
250 A - 320 A
|
Overload current setting (Ir) - min |
250 A
|
Overload current setting (Ir) - max |
320 A
|
Short delay current setting (Isd) - min |
0 A
|
Short delay current setting (Isd) - max |
0 A
|
Short-circuit release non-delayed setting - min |
1920 A
|
Short-circuit release non-delayed setting - max |
3200 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 500 V DC |
70 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 750 V DC |
70 kA
|
Electrical connection type of main circuit |
Screw connection
|
Handle type |
Rocker lever
|
Mounting Method |
Built-in device plug-in technique
|
Degree of protection |
IP20
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Position of connection for main current circuit |
Front side
|