Low-voltage switchgear

Arc Quenching Magnum DS low-voltage switchgear

Arc Quenching Switchgear reduces incident energy to a level where the switchgear will survive an electrical arc flash event, while providing enhanced safety and minimal equipment downtime. Arc Quenching switchgear meets and exceeds the arc-resistant testing requirements of C37.20.7 by demonstrating acceptance even when breakers are removed, doors are open, covers are removed, and without the need for ducts, plenums or special enclosure construction.

Watch the Arc Quenching Switchgear video overview.

VOLTAGE CLASS
Up to 600 V
CONTINUOUS CURRENT
Up to 6000 A
SHORT-CIRCUIT WITHSTAND
Up to 100 kA

Core features

  • Certified UL 1558 and third party tested to ANSI/IEEE C37.20.7, Type 2B arc-resistant test guide in standard NEMA 1 construction
  • Arc Quenching Device is a UL Recognized Component per UL 2748 for arcing fault quenching equipment
  • Short circuit withstand rating up to 100 kA
  • <4 ms arc quenching time
  • Reduces incident energy to below 1.2 cal/cm2, per IEEE 1584, Guide for Performing Arc-Flash Hazard Calculations
  • Current limiting – at least 25% reduction in peak fault current
  • At least 44% reduction in peak system stress
  • Complete system self-supervision with health status communicated via Modbus and dry contacts
  • Anti-nuisance trip technology
  • Available in rear access and front access switchgear configurations
  • Available in NEMA 1, NEMA 3R and traditional arc-resistant enclosure types  

Learn more about Arc Quenching Switchgear from our educational video series.

    A digital transformation is here

    Introducing Magnum PXR switchgear. Our next generation of switchgear builds on the proven capabilities of the Magnum DS platform, now with Power Xpert Release trip units, additional mechanical features and an updated look.
    eaton-magnum-pxr-promo-500x250.jpg

    Reduced incident energy

    Arc Quenching Switchgear detects and extinguishes an electrical arc flash in less than 4 ms – dramatically reducing incident energy below 1.2 cal/cm² and reacting 10x faster than systems that rely solely on circuit breakers to clear an arc fault, including maintenance switches, zone selective interlocking (ZSI), bus differential relaying and arc detection relays.

    Enhanced arc flash safety

    Arc Quenching Switchgear meets and exceeds ANSI/IEEE C37.20.7 Type 2B arc-resistant testing requirements with breakers removed and breaker, secondary or cable compartment doors open, delivering the highest level of arc flash protection without the need for ducts, plenums, special enclosure construction or venting into the room.

    Switchgear arc protection

    Arc Quenching Switchgear minimizes or eliminates damage to switchgear in the event of an arc fault, protecting valuable switchgear assets from electrical arc flash damage. It is designed to reduce peak fault current by at least 25% and peak stress on upstream equipment by at least 44% when compared to a bolted fault device.

    Reduced downtime

    Arc Quenching Switchgear employs the Eaton Arc Flash Relay which utilizes advanced algorithms to prevent nuisance tripping of the Arc Quenching Device (AQD). Should an electrical arc flash occur, restoring service can be accomplished within hours.

    Automatic transfer schemes

    When providing redundant power sources for critical power applications, select the:

    • Eaton ATC-900 controller for lineups with main-main, main-generator or generator-generator applications
    • Eaton PLC with Eaton touchscreen for automatic main-tie-main transfer
    • Eaton Power Xpert Dashboard to monitor or control transfer schemes for a main-tie-main and adjust settings and sequence details

    Modernize and extend the life of Magnum DS low-voltage switchgear

    Genuine Magnum DS switchgear accessories and replacement parts improve the reliability, safety and longevity of the switchgear.
    Specifications

    Ratings

    VOLTAGE
    Up to 600 V
    CONTINUOUS MAIN BUS CURRENT 1,600 A to 10,000 A
    SHORT-CIRCUIT WITHSTAND Up to 100 kA
    CIRCUIT BREAKER AMPS Up to 6,000 A

    Standards

    ANSI / IEEE C37.20.1, C37.51, C37.20.7
    UL
    1558, 1066, 2748
    CSA
    C22.2 No. 31-10
    OTHER CERTIFICATIONS ABS
    SEISMIC QUALIFICATION IBC, CBC, UBC Zone 4

    Enclosure

    CONSTRUCTION
    Metal-enclosed
    POWER TERMINATIONS Rear access, Front access
    INSULATING MEDIUM
    Air
    ENCLOSURE TYPE NEMA 1 indoor, NEMA 3R outdoor
    INDOOR SECTION DIMENSIONS 18-60” w x 40-90” d x 96” h

    Devices

    OVERCURRENT PROTECTION Power circuit breaker, UL 1066
    DEVICE MOUNTING Draw-out