Arc-resistant Magnum DS low-voltage switchgear (ArcGard)

Arc-resistant switchgear is designed to safely contain and redirect arc flash energy away from the operator. Eaton's ArcGard Arc-resistant Magnum DS switchgear has been tested in all three compartments for a full 0.5 seconds (30 cycles), passing the ANSI/IEEE C37.20.7, Type 2B test guide at 100 kA, 508V and 85 kA, 635V, including an industry-exclusive Type 2B rating for the secondary door above the breakers.

LVA profile arc resistant type 2b secondary doors 500x500
VOLTAGE CLASS
Up to 600 V
CONTINUOUS CURRENT
Up to 6000 A
SHORT-CIRCUIT WITHSTAND
Up to 100 kAIC

Core features

  • Third party tested to IEEE C37.20.7 test guide for arc-resistant switchgear
  • Draw-out low voltage power circuit breakers while maintaining Type 2B rating
  • Engineered-to-order configurations
  • UL 1558, rear access cable compartment
  • Short circuit withstand rating up to 85kAIC @ 635Vac and up to 100kAIC @ 508Vac
  • 30 cycle (0.5 second) short-time withstand rating
  • Up to 10,000A continuous current –horizontal main bus
  • Up to 5,000A continuous current – vertical riser bus
  • Plenum & direct venting available to direct arc gasses to top of the enclosure
  • NEMA 1 enclosure, with either top or bottom cable or bus duct entry 

Certified to enhance safety.

ANSI Type 2B is certified arc-resistant around the entire perimeter of the equipment, even when the low voltage instrument compartment door and the secondary door above the breaker door are open. Type 2B rating offers superior protection against arcs in breaker, bus or cable compartments with no increase in footprint over Magnum DS switchgear.

Low-voltage switchgear 3D interactive

Learn about the Magnum DS, front access and arc-resistant low-voltage switchgear designs

Automatic Transfer Schemes

When providing redundant power sources for critical power applications, specify the:

- Eaton ATC-900 controller for lineups with main-main, main-generator or generator-generator applications

- Eaton PLC with Eaton touchscreen for automatic main-tie-main transfer

- Eaton Power Xpert™ Dashboard to monitor or control transfer schemes for a main-tie-main and adjust settings and sequence details

Modernize and extend the life of Magnum DS low-voltage switchgear

Genuine Magnum DS switchgear accessories and replacement parts improve the reliability, safety and longevity of the switchgear.