Foto ir ilustratīvs
Download
Eaton Moeller® series DILEM Contactor, 230 V 50 Hz, 240 V 60 Hz, 3 pole, 380 V 400 V, 4 kW, Contacts N/C = Normally closed= 1 NC, Screw terminals, AC operation DILEM-01(230V50HZ,240V60HZ)
Product Name |
Eaton Moeller® series DILEM Mini contactor
|
Catalog Number |
051795
|
EAN |
4015080517955
|
Product Length/Depth |
52 mm
|
Product Height |
58 mm
|
Product Width |
45 mm
|
Product Weight |
0.17 kg
|
Certifications |
CE
UL 508 CSA-C22.2 No. 14-05 UL Category Control No.: NLDX IEC/EN 60947-4-1 CSA Class No.: 3211-04 VDE 0660 UL File No.: E29096 UL CSA File No.: 012528 IEC/EN 60947 CSA |
Catalog Notes |
Also tested according to AC-3e.
|
Model Code |
DILEM-01(230V50HZ,240V60HZ)
|
Features |
Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module
|
Fitted with: |
Auxiliary contact
|
Number of poles |
Three-pole
|
Application |
Mini Contactors for Motors and Resistive Loads
|
Lifespan, mechanical |
150,000 Operations (at 240 V, DC, L/R = 50 ms: 2 contacts in series 0.5 A)
10,000,000 Operations 7,000,000 Operations (Coil 50/60 Hz) 200,000 Operations (at 240 V, AC-15) |
Mounting position |
As required (except vertical with terminals A1/A2 at the bottom)
|
Operating frequency |
9000 mechanical Operations/h
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Contactors
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Shock resistance |
10 g, N/O main contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
20 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/C auxiliary contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 20 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Suitable for |
Also motors with efficiency class IE3
|
Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
Voltage type |
AC
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Terminal capacity (flexible with ferrule) |
1 x (0.75 - 1.5) mm²
2 x (0.75 - 1.5) mm² |
Terminal capacity (solid) |
2 x (0.75 - 2.5) mm²
1 x (0.75 - 2.5) mm² |
Terminal capacity (solid/stranded AWG) |
18 - 14
|
Stripping length (main cable) |
8 mm
|
Screwdriver size |
2, Terminal screw, Pozidriv screwdriver
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver |
Tightening torque |
1.2 Nm, Screw terminals
|
Rated breaking capacity at 220/230 V |
90 A
|
Rated breaking capacity at 380/400 V |
90 A
|
Rated breaking capacity at 500 V |
64 A
|
Rated operational power at AC-3, 240 V, 50 Hz |
2.5 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
4 kW
|
Rated operational power at AC-3, 415 V, 50 Hz |
4.3 kW
|
Rated breaking capacity at 660/690 V |
42 A
|
Rated making capacity up to 440 V (cos phi to IEC/EN 60947) |
110 A
|
Rated operational power at AC-4, 220/230 V, 50 Hz |
1.5 kW
|
Rated operational power at AC-4, 240 V, 50 Hz |
1.8 kW
|
Rated operational power at AC-4, 415 V, 50 Hz |
3.1 kW
|
Rated operational power at AC-4, 440 V, 50 Hz |
3.3 kW
|
Rated operational power at AC-4, 500 V, 50 Hz |
3 kW
|
Rated operational power at AC-4, 660/690 V, 50 Hz |
3 kW
|
Rated operational voltage (Ue) at AC - max |
690 V
|
Rated insulation voltage (Ui) |
690 V
|
Rated operational current (Ie) |
2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series) 0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series) 1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series) |
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
22 A
|
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
6 A
|
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V |
3 A
|
Rated operational current (Ie) at AC-15, 500 V |
1.5 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
9 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
9 A
|
Rated operational current (Ie) at AC-3, 440 V |
9 A
|
Rated operational current (Ie) at AC-3, 500 V |
6.4 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
4.8 A
|
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
6.6 A
|
Rated operational current (Ie) at AC-4, 440 V |
6.6 A
|
Rated operational current (Ie) at AC-4, 500 V |
5 A
|
Rated operational current (Ie) at AC-4, 660 V, 690 V |
3.4 A
|
Rated operational current (Ie) at DC-1, 110 V |
20 A
|
Rated operational current (Ie) at DC-1, 12 V |
20 A
|
Rated operational current (Ie) at DC-1, 220 V |
20 A
|
Rated operational current (Ie) at DC-1, 24 V |
20 A
|
Rated operational current (Ie) at DC-1, 60 V |
20 A
|
Safe isolation |
300 V AC, Between coil and auxiliary contacts, According to EN 61140
300 V AC, Between the contacts, According to EN 61140 300 V AC, Between auxiliary contacts, According to EN 61140 300 V AC, Between coil and contacts, According to EN 61140 |
Short-circuit current rating (basic rating) |
5 kA, SCCR (UL/CSA)
45 A, max. Fuse, SCCR (UL/CSA) |
Short-circuit protection |
10 A fast, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding
PKZM0-4, Maximum overcurrent protective device, Short-circuit protection only, Auxiliary contacts, Short-circuit rating without welding 6 A gG/gL, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding |
Short-circuit protection rating (type 1 coordination) at 500 V |
20 A gG/gL
|
Short-circuit protection rating (type 2 coordination) at 500 V |
10 A gG/gL
|
Conventional thermal current Ith (1-pole, enclosed) |
40 A
|
Conventional thermal current Ith (3-pole, enclosed) |
16 A
|
Conventional thermal current Ith at 55°C (3-pole, open) |
19 A
|
Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
10 A
|
Conventional thermal current Ith of main contacts (1-pole, open) |
50 A
|
Switching capacity (main contacts, general use) |
15 A, Maximum motor rating (UL/CSA)
|
Switching capacity (auxiliary contacts, general use) |
10 A, 600 V AC, (UL/CSA)
0.5 A, 250 V DC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
P300, DC operated (UL/CSA)
A600, AC operated (UL/CSA) |
Arcing time |
12 ms at 690 V AC
|
Changeover time |
16 - 21 ms
|
Duty factor |
100 %
|
Pick-up voltage |
1.1 V AC x Uc (voltage tolerance - dual frequency coil 50/60 Hz)
0.8 - 1.1 V AC x Uc (voltage tolerance - single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz) |
Power consumption, pick-up, 50 Hz |
25 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
22 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
Power consumption, pick-up, 60 Hz |
22 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
25 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
Power consumption, sealing, 50 Hz |
4.6 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
1.8 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
Power consumption, sealing, 60 Hz |
1.8 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
230 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
240 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Switching time (AC operated, make contacts, closing delay) - min |
14 ms
|
Switching time (AC operated, make contacts, closing delay) - max |
21 ms
|
Switching time (AC operated, make contacts, opening delay) - min |
8 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
18 ms
|
Switching time (AC operated, N/O, with auxiliary contact module, closing delay) |
45 ms
|
Assigned motor power at 115/120 V, 60 Hz, 1-phase |
0.5 HP
|
Assigned motor power at 200/208 V, 60 Hz, 3-phase |
2 HP
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
1.5 HP
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase |
3 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
5 HP
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
5 HP
|
Control circuit reliability |
< 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
|
Number of auxiliary contacts (normally closed contacts) |
1
|
Number of auxiliary contacts (normally open contacts) |
0
|
Equipment heat dissipation, current-dependent Pvid |
1.2 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0.4 W
|
Rated operational current for specified heat dissipation (In) |
9 A
|
Static heat dissipation, non-current-dependent Pvs |
1.8 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|