Lejupielādēt dokumentu () no 20

190845
Modeļa kods: FAZ-B1,5/4-RT

Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB. Miniature circuit breaker (MCB), 1.5 A, 4p, characteristic: B, ring tongue

Vispārējā informācija

Product Name
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB
Catalog Number
190845
EAN
4015081904921
Product Length/Depth
105 mm
Product Height
75.5 mm
Product Width
70.8 mm
Product Weight
0.496 kg
Compliances
RoHS conform
Certifications
CSA-C22.2 No. 5-09
North America (UL listed, CSA certified)
UL (Category Control Number DIVQ)
CE marking
CSA (Class No. 1432-01)
CSA (File No. 204453)
UL 489, CSA C22.2 No. 5
IEC 60947-2
UL (File No. E235139)
Specially designed for North America, suitable as BCPD
IEC/EN 60947-2
UL 489
EN45545-2
IEC 61373
Model Code
FAZ-B1,5/4-RT

Delivery program

Application
  • Feeder circuits, branch circuits
  • Switchgear for export to North America (UL-listed)
  • xEffect - Switchgear for industrial and advanced commercial applications
Number of poles
Four-pole
Number of poles (total)
4
Number of poles (protected)
4
Tripping characteristic
B
Release characteristic
B
Amperage Rating
1.5 A
Type
  • FAZ-RT
  • Miniature circuit breaker

Technical Data - Electrical

Voltage type
AC
Voltage rating
277 V AC / 480 V AC
Voltage rating at DC
60 V DC
Voltage rating (IEC/EN 60947-2)
440 V
Voltage rating (UL)
480Y/277 V
Rated operational voltage (Ue) - max
240 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated switching capacity (IEC/EN 60947-2)
15 kA
Operational switching capacity
7.5 kA
Breaking capacity
10 kA (UL489)
Admissible back-up fuse - max
125 A gL/gG
Selectivity class
3
Lifespan, electrical
min. 1500 operations
min. 6000 operations (UL)
Overvoltage category
III
Pollution degree
2
Direction of incoming supply
As required

Technical Data - Mechanical

Frame
45 mm
Enclosure width
105 mm
Width in number of modular spacings
4
Built-in depth
60 mm
Mounting width
17.7 mm
Mounting width per pole
17.7 mm
Mounting Method
Top-hat rail IEC/EN 60715
Mounting position
As required
Degree of protection
IP20
IP20 (IEC)
IP40 (when fitted)
UL/CSA Type: -
Terminals (top and bottom)
Lift terminal / ring-tongue
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²
Terminal capacity of screw terminals for main cable
10 mm² (2x)
Terminal capacity (control cable)
25 mm² (1x)
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Contact position indicator color
Red / green
Tightening torque
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
Max. 2.4 Nm
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
UL: 4 Nm (36 lb-in) for AWG 6
Lifespan, mechanical
10000 operations

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
1.5 A
Heat dissipation per pole, current-dependent
0 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
75 °C
Ambient operating temperature (UL) - min
-5 °C
Ambient operating temperature (UL) - max
40 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Accessories required
Z-IHK-NA 113895
Current limiting class
3
Features
Additional equipment possible
Fitted with:
Z-IS/SPE-1TE 274418
Functions
Current limiting circuit breaker
Internal resistance at room temperature (single-pole, 50 Hz)
900 mΩ
Special features
  • Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
  • Tripping signal contact for subsequent installation Z-NHK 248434
Suitable for
Flush-mounted installation
Used with
FAZ-XAA-NA110-415V AC 102036 (Shunt trip release) FAZ-XAA-NA12-110V AC 102037 (Shunt trip release)
Miniature circuit breaker
FAZ-RT
FAZ-XAA-NA110-415V AC 102036 (Shunt trip release)
FAZ-XAA-NA12-110V AC 102037 (Shunt trip release)

Eksportēt produkta specifikāciju

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autentificēt produktu

Ievadiet savu 16–17 ciparu sērijas numuru
Jūsu ievadītais sērijas numurs nedrīkst ietvert speciālo rakstzīmi. Jūsu ievadītais sērijas numurs nav pareizs – tam jābūt 16 vai 17 cipariem. Jūsu ievadītais sērijas numurs netika atrasts Lūdzu, mēģiniet vēlreiz vai ziņot par problēmu turpmākai palīdzībai. Jūsu ievadītais sērijas numurs neatbilst produktam. Pārbaudiet produkta sērijas numuru un mēģiniet vēlreiz. Noklikšķiniet šeit , lai pārietu uz produktu lapu jūsu ievadītajam sērijas numuram Sērijas numurs Eaton ir zināms kā aizdomīgs, lūdzu, mēģiniet vēlreiz vai ziņot par problēmu turpmākai palīdzībai.
Sērijas numurs
Atiestatīt Sērijas numurs Eaton ir zināms kā aizdomīgs, lūdzu, mēģiniet vēlreiz vai ziņot par problēmu turpmākai palīdzībai. Eaton neatpazīst sērijas numuru, un tas nav derīgs. Lūdzu, izmantojiet šo veidlapu, lai ziņot par problēmu turpmākai palīdzībai.
Ievadiet 6 ciparu autentifikācijas kodu
Jūsu ievadītais produkts ir aizdomīgs! Lūdzu, mēģiniet vēlreiz vai ziņot par problēmu turpmākai palīdzībai. Jūsu ievadītais autentifikācijas kods neatbilst mūsu ierakstiem par šo sērijas numuru. Lūdzu, mēģiniet vēlreiz vai ziņot par problēmu turpmākai palīdzībai. Nederīgs autentifikācijas kods. Garumam jābūt 6 rakstzīmēm ziņot par problēmu turpmākai palīdzībai. Jānorāda autentifikācijas kods ziņot par problēmu turpmākai palīdzībai.
Izpildiet Captcha uzdevumu pirms autentifikācijas.
Sazinieties ar mums zinot-problemu
x
Ziņot par problēmu
Lūdzu, ievadiet savu vārdu un uzvārdu.
x
Paldies, ziņojums par jūsu problēmu ir iesniegts, mūsu produktu atbalsta komanda drīzumā ar jums sazināsies.
Piezīme. Ja .zip lejupielādes failā trūkst fails(-i), lielapjoma lejupielāde neatbalsta faila tipu.