Wyszukiwanie informacji
Pobierz dokument () Wyszukiwania 20
Sprawiamy, że to co ważne działa.*

168508
Kod modelu: NZMN3-4-A320-SVE

Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 4p, 320A, plug-in module, NZMN3-4-A320-SVE

General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
Catalog Number
168508
EAN
4015081649860
Product Length/Depth
335 mm
Product Height
215.2 mm
Product Width
185 mm
Product Weight
8.81 kg
Compliances
RoHS conform
Model Code
NZMN3-4-A320-SVE

Delivery program

Application
Use in unearthed supply systems at 690 V
Accessories required
NZM3-XSVS
Number of poles
Four-pole
Amperage Rating
320 A
Features
Motor drive optional
Protection unit
Special features
Rated current = rated uninterrupted current: 320 A

Technical Data - Electrical

Voltage rating
690 V - 690 V
Current rating of neutral conductor
200% of phase conductor
Amperage Rating
320 A
Instantaneous current setting (Ii) - min
1920 A
Instantaneous current setting (Ii) - max
19200 A
Overload current setting (Ir)
250 A - 320 A
Overload current setting (Ir) - min
250 A
Overload current setting (Ir) - max
320 A
Short-circuit release non-delayed setting - min
1920 A
Short-circuit release non-delayed setting - max
3200 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 500 V DC
30 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 750 V DC
30 kA
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
330 kA
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever

Technical Data - Mechanical

Mounting Method
Built-in device plug-in technique
Mounting Method
Built-in device plug-in technique
Degree of protection
IP20
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Front side
Special features
Rated current = rated uninterrupted current: 320 A

Technical Data - Mechanical - Terminals

Optional terminals
Box terminal. Connection on rear. Tunnel terminal
Terminal capacity (copper busbar)
Max. 30 mm x 10 mm + 30 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper strip)
10 segments of 50 mm x 1 mm (2x) at rear-side width extension
Max. 10 segments of 32 mm x 1 mm + 5 segments of 32 mm x 1 mm at rear-side connection (punched)
Min. 6 segments of 16 mm x 0.8 mm at rear-side connection (punched)

Design verification as per IEC/EN 61439 - technical data

Equipment heat dissipation, current-dependent
94 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Eksport specyfikacji produktu

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Uwierzytelnianie produktu

Wprowadź swój 16-17-cyfrowy numer seryjny
Wprowadzony numer seryjny nie powinien zawierać znaków specjalnych. Wprowadzony numer seryjny jest nieprawidłowy i powinien składać się z 16 lub 17 cyfr. Wprowadzony numer seryjny nie został znaleziony. Spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Wprowadzony numer seryjny nie jest zgodny z produktem. Sprawdź numer seryjny produktu i spróbuj ponownie. Kliknięcie informacje. aby przejść do strony produktu dla wprowadzonego numeru seryjnego Numer seryjny jest podejrzany według danych Eaton, spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc.
Numer seryjny
Reset Numer seryjny jest podejrzany według danych Eaton, spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Numer seryjny jest nieprawidłowy i nie został rozpoznany przez firmę Eaton. Użyj tego formularza, aby zgłoś ten problem aby uzyskać dalszą pomoc.
Wprowadź 6-cyfrowy kod uwierzytelniania
Wprowadzony produkt jest podejrzany! Spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Wprowadzony kod uwierzytelnienia nie jest zgodny z naszymi danymi dla tego numeru seryjnego. Spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Nieprawidłowy kod uwierzytelnienia. Długość musi wynosić 6 znaków zgłoś ten problem aby uzyskać dalszą pomoc. Kod uwierzytelniający jest wymagany zgłoś ten problem aby uzyskać dalszą pomoc.
Wykonaj wyzwanie Captcha przed uwierzytelnieniem.
Skontaktuj się z nami do zgłoszenia problemu
x
Zgłaszanie problemu
Wprowadź swoje imię i nazwisko.
x
Dziękujemy, Twoje zgłoszenie zostało przyjęte. Nasz zespół produktowy wkrótce się z Tobą skontaktuje.
Uwaga: Jeśli w pobieraniu .zip nie ma pliku(-ów), typ pliku nie jest obsługiwany przez pobieranie zbiorcze.