Medium-voltage transformers

PEAK single-phase overhead transformer

Eaton’s Cooper Power series single-phase overhead PEAK transformers provide the capability to manage increased loads and temporary overload conditions without accelerating loss of insulation system life, compared to mineral oil-filled alternatives. The transformers’ overload capacity enables utilities to operate beyond full-rated load to at least 109 %, while their smaller, lighter footprint further enhances value.

Voltage class
5-167 kVA
Average winding rise (AWR) / slash ratings
75˚ C / 55/75 °C and 65/75 °C
Primary voltage
2400-34,500 V

Core features

  • PEAK transformers are designed to improve performance with longer insulation life and offer compact dimensions, lighter weight, safety and sustainability
  • Superior moisture and thermal stress managing capabilities allow for extended insulation system life and enhanced reliability
  • Utilizes an advanced high-temperature insulation system comprised of thermally upgraded kraft paper, FR3 dielectric fluid and an optimized core and coil design
  • Available in 5-167 kVA single-phase pole-mount designs; 75 °C AWR and 65/75 °C AWR options
  • 75 °C Average Winding Rise (AWR) of PEAK transformer offers the same ratings as a physically larger and heavier 65 °C AWR rated unit
  • A 65/75 °C slash rated PEAK transformer is comparable in size to a conventional transformer but has nameplated overload capability
  • Meets or exceeds industry standards including ANSI, NEMA and DOE Energy Efficiency
  • Available in conventional or CSP designs for various overcurrent protection options
  • Cores and coils designed for high reliability and low field failure rates: Available in grain-oriented electrical or amorphous steel

Better manage temporary overload capacity

PEAK single-phase transformers can be loaded continuously 9% beyond full-rated base load, helping utilities to more precisely size transformers based on periods of peak demand — without accelerated reduction of insulation life.

Gain additional load capacity

Designed to accommodate heavier base loading for longer periods without accelerating loss of insulation system life, PEAK single-phase transformers can be loaded continuously 9% beyond full rated base load.

Improve reliability

With superior moisture and thermal stress managing capabilities, PEAK transformers extend insulation system life, improving overall system reliability by reducing outages and transformer failures.
Specifications

Ratings

  • PEAK 50 or 60 Hz (5-167 kVA)
    • Overload capacity: At least 109%
    • Standard with FR3 dielectric fluid
    • Primary voltage: 2400-34,500 V
    • Secondary voltage: 120-600 V

Specifications

  • Meets or exceeds ANSI, NEMA and DOE2016 standards
    • IEEE, C57.12.00, C57.12.20, C57.12.31, C57.12.35, C57.12.90, C57. 91 and C57.154
    • NEMA standards, NEMA TR 1 (R2000)
    • Department of Energy Efficiency Standard, 10 CFR Part 431
  • Tank coating exceeds IEEE Std C57.12.31-2010 standard
  • Cover with a minimum dielectric strength of 8 kV
  • FR3 fluid
  • Cores and coils designed for high reliability and low field failure rates: Available in grain-oriented electrical or amorphous steel
  • Heavy-duty lifting lugs and hanger brackets per ANSI requirements up to 4500 lbs
  • The transformer shall be designed in accordance with this specification and shall have an Average Winding Rise (AWR) of one of the following:
    • 55/75 °C, 65/75 °C, 75 °C
    • The applicable AWR rating shall be specified on the inquiry
  • The transformer shall be designed in accordance with this specification and shall have one of the following kVA ratings:
    •  5, 10, 15, 25, 37.5, 50, 75, 100, 167
    • The applicable kVA rating shall be specified on the inquiry
  • Quality System ISO 9001 certified