Medium-voltage transformers

Envirotran hardened data center substation transformer

Eaton’s Cooper Power series Envirotran Hardened Data Center (HDC) three-phase substation transformer provides superior performance and surge protection even in stressful electrical environments. Designed and built around superior efficiency and reliability, substation HDC Transformers can be utilized in both indoor and outdoor applications, stepping down a wide variety of distribution system voltages while meeting an extensive array of complex data center needs including relaying protection, advanced monitoring and VFI fault protection.  

Base rating
300 kVA to 12,000 kVA
Primary voltage
2400-46,000 V (Delta or Wye connected)
Secondary voltage
208Y/120 V to 14,400 V

Core features

  • Not reliant on a RC snubber circuit for transient surge protection
  • Readily biodegradable and non-toxic FR3 fluid provides sustainable, highly efficient performance at a low cost
  • Provides overload capability above nameplate without significant loss of life
  • Higher BIL and more optimum resonant frequency prevent damage from potentially harmful switching overvoltages
  • UL Classified, FM approved and NEC compliant for indoor applications that meet a wide variety of commercial, industrial and utility needs
  • Seismic rated available

Unparalleled combination of reliability, efficiency, safety and performance

Eaton's Cooper Power series HDC substation transformers offer superior technology with reduced operating costs, improved power usage effectiveness (PUE), increased fire protection and operational life.

Are snubbers required with Eaton’s Cooper Power series liquid-filled hardened transformers?

Studies have shown that Eaton’s Cooper Power series hardened substation transformers do not require snubbers to protect against transient switching voltages.

Superior overload protection

The cooling system and enhanced BIL of Envirotran liquid-filled transformers provides superior protection from severe overloads above base nameplate rating without significant loss of life.

Optimize efficiency, reduce operating expenses

Envirotran HDC transformers can reduce HVAC operating expense to cool transformer by as much as 40%.

Save space and reduce equipment coordination

Close-couple medium-voltage liquid-filled transformers with low and medium-voltage assemblies in a streamlined unit substation design.
Specifications

Ratings

Base kVA
45 kVA to 12,000 kVA
Primary voltage
2400 V to 46,000 V
Secondary voltage
120 V to 24,940 V
Basic Impulse Level (BIL)
30kV to 250kV

Standards

ANSI/IEEE
C57.12.00 and C57.12.36
CSA
C88
NEMA (sound level)
NEMA TR-1
Third-party approval/recognition
FM Global (Indoor & Outdoor), UL/cUL – available for most ratings

Enclosure

Layout
Unit or open substation type
Tamper resistance
Three-point latching and padlock system with recessed penta-head bolt
Enclosure integrity
Meets or exceeds ANSI/IEEE C.57.12.28 andC57.12.29
Material
Mild or stainless steel (304L)
Enclosure environment
Indoor and outdoor
Insulating medium 
Air
Hinge material
Stainless steel cabinet hinges and mounting studs

Key features

Distribution transformer Three-phase substation
Install location Indoor and outdoor
Power direction Step-down and Step-up
Fluid FR3 fluid or electrical grade mineral insulating oil (upon special request)
Tap changer De-energized tap changer, externally operable
Terminations Sidewall-mounted high-voltage porcelain bushings
Sidewall-mounted low-voltage molded epoxy bushings with NEMA spades
Tank features Tank bases designed for skidding or rolling in any direction
Extra-heavy, welded-in-place lifting lugs and jack pads (4)
Cooling Cooling radiators are welded directly to the tank
Removable Radiators (optional)
Standard gauges Dial-type thermometer
Dial-type liquid level gauge
Pressure vacuum gauge
Cover mounted automatic pressure relief device
Pressure test connection
Drain/fill valves Paint color 1” upper fill plug with filter press connection
1” drain valve with sampler combination (2500 kVA and below)
2” drain valve with sampler (over 2500 kVA)
1” upper filter valve (over 2500 kVA)
Painted using ANSI #61 Light Gray; ANSI #70 Sky Gray; or special paint available per request
Grounding Stainless steel NEMA 2-hole ground pads (750-7500 kVA)
Nameplate Laser-scribed anodized aluminum nameplate (SS nameplate optional)