Download document () of 20
Medium-voltage transformers

Envirotran hardened data center three-phase pad-mounted transformer

Eaton’s Cooper Power series Envirotran Hardened Data Center (HDC) three-phase pad-mounted transformer provides superior performance and surge protection even in stressful electrical environments. Filled with FR3 dielectric fluid, pad-mounted HDC transformers can be utilized in both indoor and outdoor applications, stepping down a wide variety of distribution system voltages while meeting an extensive array of complex data center needs including relaying protection, advanced monitoring and VFI fault protection.  

Base rating
45 kVA to 12,000 kVA
Primary voltage
2400 V to 46,000 V
Secondary voltage
208Y/120 V to 24,940 V

Core features

  • Not reliant on a RC snubber circuit for transient surge protection
  • Readily biodegradable and non-toxic FR3 fluid provides sustainable, highly efficient performance at a low cost
  • Provides overload capability above nameplate without significant loss of life
  • Higher BIL and more optimum resonant frequency prevent damage from potentially harmful switching overvoltages
  • UL Classified, FM approved and NEC compliant for indoor applications that meet a wide variety of commercial, industrial and utility needs
  • Seismic rated available

Unparalleled combination of reliability, efficiency, safety, and performance

Eaton's Cooper Power series HDC pad-mounted transformers offer superior technology with reduced operating costs, improved power usage effectiveness (PUE), increased safety and operational life.

Are snubbers required with Eaton’s Cooper Power series liquid-filled hardened transformers?

Studies have shown that Eaton’s Cooper Power series hardened substation transformers do not require snubbers to protect against transient switching voltages.

Superior overload protection

The cooling system and enhanced BIL of Envirotran liquid-filled transformers provides superior protection from severe overloads above base nameplate rating without significant loss of life.

Optimize efficiency, reduce operating expenses

Envirotran HDC transformers can reduce HVAC operating expense to cool transformer by as much as 40%.
Specifications

Ratings

Base kVA
45 kVA to 12,000 kVA
Primary Voltage
2400 V to 46,000 V
Secondary Voltage
120 V to 24,940 V
Basic Impulse Level (BIL)
30 kV to 250 kV

Standards

ANSI/IEEE
C57.12.00 and C57.12.34
CSA
C227.4 
NEMA (sound level)
NEMA TR-1
Third-party approval/recognition
FM Global (Indoor & Outdoor), UL/cUL – available for most ratings

Enclosure

Layout
Compartmental type
Tamper resistance
three-point latching & padlock system with recessed penta-head bolt
Enclosure integrity
Meets or exceeds ANSI/IEEE C.57.12.28 and C57.12.29
Material 
Mild or stainless steel (304L)
Enclosure environment
Indoor and Outdoor
Insulating medium 
Air
Hinge material
Stainless steel cabinet hinges and mounting studs

Key features

Distribution transformer
Three-phase pad-mounted
Install location
Indoor and outdoor
Power direction
Step-down and Step-up
Cover
Bolted cover for tank access (45-1000 kVA)
Welded cover with handhole (1500-7500 kVA)
Surge protection
Lightning arrester mounting provisions (live-front)
Nameplate
Laser-scribed anodized aluminum nameplate (SS available) 
Drain/fill valves 
One-inch drain valve with sampling device in low-voltage compartment (45-7500 kVA) 
Pressure relief 
Automatic pressure relief device
Cabinet
20" deep cabinet (45-1000 kVA)
24" deep cabinet (1500-7500 kVA)
30" deep cabinet (34.5/19.92 kV)
Primary termination
(15, 25 kV) 200 A (HTN) bushing wells
(15, 25, 35 kV) 200 A Integral bushings (dead-front)
Electrical-grade wet-process porcelain bushings (live-front)
Lifting lugs
Certified Lifting lugs (4)
Grounding 
Stainless steel NEMA 2-hole ground pads (750-7500 kVA)