Scarica il documento () sui 20

3-4917-306A
Codice del modello: DG1-35325FB-C00C

Eaton DG1 Variable frequency drive, 600 V AC, 3-phase, 325 A, 200 kW, IP00, Brake chopper, DC link choke

General specifications

Product Name
Eaton DG1 variable frequency drive
Catalog Number
3-4917-306A
EAN
4015081941834
Product Length/Depth
561 mm
Product Height
1538 mm
Product Width
506 mm
Product Weight
410 kg
Certifications
EAC
C-Tick
RoHS, ISO 9001
UkrSEPRO
UL
CUL
CE
Safety requirements: IEC/EN 61800-5
IEC/EN 61800-3
Specification for general requirements: IEC/EN 61800-2
Model Code
DG1-35325FB-C00C

Modelli & Funzioni

Features
Temperature-controlled fan
Externally accessible fan
Functions
4-quadrant operation possible

Informazioni generali

Air volume capacity
1400 m³/h
Cable length
C3 ≤ 10 m, Radio interference level, maximum motor cable length
50 m, screened, maximum permissible, Motor feeder
Degree of protection
IP00
NEMA Other
Electromagnetic compatibility
1st and 2nd environments (according to EN 61800-3)
Environmental class
3C2, 3S2 (Air quality)
Fitted with:
Radio interference suppression filter
IGBT inverter
Brake chopper
DC link choke
Internal DC link
Additional PCB protection
Multi-line graphic display
Breaking resistance
Control unit
PC connection
Frame size
FS7
Mounting position
Vertical
Number of slots
2 (expansion)
Overvoltage category
III
Pollution degree
2
Protection
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Radio interference class
C1: with external filter, for conducted emissions only
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Safety function/level
STO (Safe Torque Off, SIL1, PLc Cat 1)
Shock resistance
UPS drop test (for weights inside the UPS frame)
Storage and transportation: maximum 15 g, 11 ms (inside the packaging)
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
Suitable for
Branch circuits, (UL/CSA)
Vibration
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6

Condizioni ambientali e climatiche

Altitude
Above 1000 m with 1 % derating per 100 m
Max. 1000 m
Max. 2000 m
Ambient operating temperature - min
-10 °C
Ambient operating temperature - max
50 °C
Ambient operating temperature at 150% overload - min
-10 °C
Ambient operating temperature at 150% overload - max
40 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
< 95 average relative humidity (RH), no condensation, no corrosion

Circuito principale

Apparent power at 690 V
460.1 kVA
Current limitation
0.1 - 2 x IH (CT), motor, main circuit
Efficiency
98.3 % (η)
Input current ILN at 110% overload
286 A
Input current ILN at 150% overload
327 A
Mains current distortion
28 %
Mains switch-on frequency
Maximum of one time every 60 seconds
Mains voltage - min
525 V
Mains voltage - max
600 V
Operating mode
Speed control with slip compensation
U/f control
Sensorless vector control (SLV)
Torque regulation
Output frequency - min
0 Hz
Output frequency - max
400 Hz
Output voltage (U2)
600 V AC, 3-phase
690 V AC, 3-phase
Overload current IL at 110% overload
423.5 A
Overload current IL at 150% overload
487.5 A
Rated conditional short-circuit current (Iq)
65 kA
Rated control supply voltage
10 V DC (Us, max. 10 mA)
Rated frequency - min
45 Hz
Rated frequency - max
66 Hz
Rated operational current (Ie) at 110% overload
385 A
Rated operational current (Ie) at 150% overload
325 A
Rated operational power at 525 V, 50 Hz
200 kW
Rated operational power at 525 V, 50 Hz, 110% overload
250 kW
Rated operational power at 600 V, 50 Hz
250 kW
Rated operational power at 600 V, 50 Hz, 110% overload
315 kW
Rated operational voltage
690 V AC, 3-phase
600 V AC, 3-phase
Resolution
0.01 Hz (Frequency resolution, setpoint value)
Short-circuit protection rating
600 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
Starting current - max
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
Supply frequency
50/60 Hz
Switching frequency
2 kHz, 1.5 - 6 kHz adjustable, fPWM, Power section, Main circuit
System configuration type
TN-S, TN-C, TN-C-S, TT, IT
Voltage rating - max
690 VAC

Potenza nominale d'impiego (Motore)

Assigned motor current IM at 525 V, 50 Hz, 110% overload
349 A
Assigned motor current IM at 525 V, 50 Hz, 150% overload
279 A
Assigned motor current IM at 600 V, 50 Hz, 110% overload
383 A
Assigned motor current IM at 600 V, 50 Hz, 150% overload
304 A
Assigned motor current IM at 690 V, 60 Hz, 110% overload
358 A
Assigned motor current IM at 690 V, 60 Hz, 150% overload
292 A
Assigned motor power at 690 V, 60 Hz
350 HP
Assigned motor power at 690 V, 60 Hz, 110% overload
450 HP

Potenza apparente

Apparent power at 600 V
400.1 kVA

Funzione di frenatura

Braking resistance
2.5 Ω
Braking torque
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Adjustable to 150 %, DC - Main circuit
Adjustable to 150 % (I/Ie), DC - Main circuit
Switch-on threshold for the braking transistor
1050 VDC

Circuito di controllo

Number of inputs (analog)
2
Number of inputs (digital)
8
Number of outputs (analog)
2
Number of outputs (digital)
1
Number of relay outputs
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
Rated control voltage (Uc)
24 V DC (external, max. 250 mA options incl.)

Comunicazione

Communication interface
DeviceNet, optional
Ethernet IP, built in
PROFIBUS, optional
Modbus RTU, built in
Modbus TCP, built in
BACnet MS/TP, built in
SmartWire-DT, optional
CANopen®, optional
Connection to SmartWire-DT
Yes
In conjunction with DXG-NET-SWD SmartWire DT module
Protocol
BACnet
CAN
DeviceNet
EtherNet/IP
MODBUS
Other bus systems
PROFIBUS
PROFINET IO
TCP/IP

Verifica di progetto

Equipment heat dissipation, current-dependent Pvid
6781 W
Rated operational current for specified heat dissipation (In)
325 A
Static heat dissipation, non-current-dependent Pvs
146 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.

Esporta le caratteristiche del prodotto