Bilgi Arama
Belgeyi İndir () / 20
Zor İşler Bizimle Kolay

266013
Model Kodu: PN2-4-250

Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 4p, 250A

General specifications

Product Name
Eaton Moeller series NZM switch-disconnector
Catalog Number
266013
EAN
4015082660130
Product Length/Depth
142 mm
Product Height
185 mm
Product Width
140 mm
Product Weight
2.422 kg
Compliances
RoHS conform
Certifications
IEC
IEC/EN 60947
Model Code
PN2-4-250

Additional information

Functions
Disconnectors/main switches
Interlockable

Delivery program

Amperage Rating
250 A
Application
Use in unearthed supply systems at 690 V
Circuit breaker frame type
PN2
Features
Version as main switch
Version as maintenance-/service switch
Version as emergency stop installation
Number of poles
Four-pole
Special features
  • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
  • Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
  • Busbar tag shroud to VDE 0160 Part 100.
  • Rated current = rated uninterrupted current: 250 A
  • The rated short-time withstand current for PN2/N2 in conjunction with earth-fault release NZM2-4-XFI...Icw = 1.5 kA
Type
Switch-disconnector

Design verification as per IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature - max
70 °C
Ambient storage temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - min
40 °C
Equipment heat dissipation, current-dependent
48 W
Rated operational current for specified heat dissipation (In)
250 A

Technical Data - Electrical

Amperage Rating
250 A
Direction of incoming supply
As required
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Lifespan, electrical
7500 operations at 400 V AC-1
6000 operations at 400 V AC-3
6000 operations at 415 V AC-3
7500 operations at 415 V AC-1
5000 operations at 690 V AC-1
4000 operations at 690 V AC-3
Number of operations per hour - max
120
Overvoltage category
III
Pollution degree
3
Rated conditional short-circuit current with back-up fuse
100 kA at 400/415 V
80 kA at 690 V
PN2(N2)-160…250: 250 AgGgL
Rated conditional short-circuit current with downstream fuse
PN2(N2)-160…250: 250 AgGgL
100 kA at 400/415 V
80 kA at 690 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated insulation voltage (Ui)
690 V
Rated operating frequency
50 Hz
Rated operating power at AC-23, 400 V
132 kW
Rated operating voltage (Ue) at AC - max
690 V
Rated operational current
250 A (415 V AC-22/23A, making and breaking capacity)
250 A (690 V AC-22/23A, making and breaking capacity)
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
5.5 kA
Rated short-time withstand current (Icw)
3.5 kA
Rated short-time withstand current (t = 0.3 s)
3.5 kA
Rated short-time withstand current (t = 1 s)
3.5 kA
Short-circuit protective device fuses - max
250 A gL
Voltage rating
690 V - 690 V

Technical Data - Mechanical

Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Degree of protection
IP20 (basic protection type, in the area of the HMI devices)
Other
Degree of protection (IP), front side
IP20
IP40 (with insulating surround)
IP66 (with door coupling rotary handle)
Degree of protection (terminations)
IP00 (terminations, phase isolator and band terminal)
IP10 (tunnel terminal)
Handle color
Black
Lifespan, mechanical
20000 operations
Mounting Method
Built-in device fixed built-in technique
Intermediate mounting
Fixed
Ground mounting
Distribution board installation
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Number of switches
1
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Special features
  • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
  • Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
  • Busbar tag shroud to VDE 0160 Part 100.
  • Rated current = rated uninterrupted current: 250 A
  • The rated short-time withstand current for PN2/N2 in conjunction with earth-fault release NZM2-4-XFI...Icw = 1.5 kA
Switch positions
I, 0

Technical Data - Mechanical - Terminals

Optional terminals
Box terminal. Connection on rear. Tunnel terminal
Standard terminals
Screw terminal
Terminal capacity (aluminum solid conductor/cable)
16 mm² (1x) at tunnel terminal
10 mm² - 16 mm² (1x) direct at switch rear-side connection
10 mm² - 16 mm² (2x) direct at switch rear-side connection
Terminal capacity (aluminum stranded conductor/cable)
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal
Terminal capacity (copper busbar)
Max. 24 mm x 8 mm direct at switch rear-side connection
Min. 16 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection
Terminal capacity (copper solid conductor/cable)
10 mm² - 16 mm² (1x) direct at switch rear-side connection
10 mm² - 16 mm² (1x) at box terminal
6 mm² - 16 mm² (2x) at box terminal
6 mm² - 16 mm² (2x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
Terminal capacity (copper stranded conductor/cable)
25 mm² - 70 mm² (2x) at box terminal
25 mm² - 185 mm² (1x) at box terminal
25 mm² - 70 mm² (2x) direct at switch rear-side connection
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal
25 mm² - 185 mm² (1x) direct at switch rear-side connection
Terminal capacity (copper strip)
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 8 segments of 15.5 mm x 0.8 mm (2x) at box terminal
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Max. 10 segments of 24 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segments of 9 mm x 0.8 mm at box terminal

Ürün teknik özelliklerini aktar

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Ürünü Doğrula

16 veya 17 haneli seri numaranızı girin.
Girdiğiniz seri numarası özel karakter içermemelidir. Girdiğiniz seri numarası doğru değil, seri numarası 16 veya 17 haneli olmalıdır. Girdiğiniz seri numarası bulunamadı. Lütfen tekrar deneyin veya Bu sorunu bildir daha fazla destek için. Girdiğiniz seri numarası ürünle eşleşmiyor. Girdiğiniz seri numarası ürünle eşleşmiyor. Tıkla buraya Girdiğiniz seri numarasına ait ürün sayfasına gitmek için… Bu seri numarası Eaton tarafından şüpheli olarak tanımlanmıştır, lütfen tekrar deneyin veya… Bu sorunu bildir daha fazla destek için.
Seri numarası
Sıfırla Bu seri numarası Eaton tarafından şüpheli olarak tanımlanmıştır, lütfen tekrar deneyin veya… Bu sorunu bildir daha fazla destek için. Bu seri numarası Eaton tarafından tanınmıyor ve geçersiz. Lútfen bu formu kullanın Bu sorunu bildir daha fazla destek için.
6 haneli doğrulama kodunu girin.
Girdiğiniz ürün şüpheli görünüyor! Lütfen tekrar deneyin veya Bu sorunu bildir daha fazla destek için. Girdiğiniz doğrulama kodu bu seri numarası için kayıtlarımızla eşleşmiyor. Lütfen tekrar deneyin veya Bu sorunu bildir daha fazla destek için. Geçersiz Doğrulama kodu. Doğrulama kodu 6 haneden oluşmalıdır. Bu sorunu bildir daha fazla destek için. Doğrulama kodu gereklidir Bu sorunu bildir daha fazla destek için.
Doğrulama işleminden önce, Captcha güvenlik doğrulamasını tamamlayın.
Bize Ulaşın Bir sorunu bildirmek için
x
Sorun Bildirin
Lütfen tam adınızı girin.
x
Teşekkür ederiz, talebiniz alındı. Ürün ekibimiz sizinle kısa süre içinde iletişime geçecek.
Not: .zip indirmesinde dosya(lar) eksikse dosya türü toplu indirme tarafından desteklenmiyor demektir.