Pobierz dokument () Wyszukiwania 20

170746
Kod modelu: FRBMM-C20/3/01-A

Eaton Moeller series xEffect - FRBm6/M RCBO - residual-current circuit breaker with overcurrent protection. RCD/MCB, 20A, 100mA, MCB trip type C, 3p, RCCB trip type: A

General specifications

Product Name
Eaton Moeller series xEffect - FRBmM RCBO - residual-current circuit breaker with overcurrent protection
Catalog Number
170746
EAN
4015081673124
Product Length/Depth
80 mm
Product Height
75.5 mm
Product Width
70 mm
Product Weight
0.39 kg
Compliances
CE Marked
RoHS conform
Certifications
CE
EN45545-2
IEC 61373
Model Code
FRBMM-C20/3/01-A

Delivery program

Application
Switchgear for industrial and advanced commercial applications
Product range
FRBmM
Basic function
Combined RCD/MCB devices
Number of poles
Three-pole
Number of poles (protected)
3
Number of poles (total)
3
Tripping characteristic
C
Release characteristic
C
Amperage Rating
20 A
Rated current
20 A
Fault current rating
0.1 A
Sensitivity type
Pulse-current sensitive
Type
RCBO

Technical Data - Electrical

Voltage type
AC
Voltage rating
415 V - 415 V
Rated operational voltage (Ue) - max
415 V
Rated insulation voltage (Ui)
500 V
Rated impulse withstand voltage (Uimp)
4 kV
Rated fault currents of product range
10, 30, 100, 300 MilliAmpere
Impulse withstand current
Partly surge-proof, 250 A
Frequency rating
50 Hz
Leakage current type
A
Rated switching capacity
10 kA
Rated switching capacity (IEC/EN 61009)
10 kA
Rated short-circuit breaking capacity (EN 60947-2)
15 kA
Rated short-circuit breaking capacity (EN 61009)
10 kA
Rated short-circuit breaking capacity (EN 61009-1)
10 kA
Rated short-circuit breaking capacity (IEC 60947-2)
15 kA
Surge current capacity
0.25 kA
Disconnection characteristic
Undelayed
Tripping
Non-delayed
Pollution degree
2

Technical Data - Mechanical

Width in number of modular spacings
4
Built-in depth
75.5 mm
Mounting Method
DIN rail
Degree of protection
IP20
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
20 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
9.2 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Current limiting class
3

Eksport specyfikacji produktu

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Uwierzytelnianie produktu

Wprowadź swój 16-17-cyfrowy numer seryjny
Wprowadzony numer seryjny nie powinien zawierać znaków specjalnych. Wprowadzony numer seryjny jest nieprawidłowy i powinien składać się z 16 lub 17 cyfr. Wprowadzony numer seryjny nie został znaleziony. Spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Wprowadzony numer seryjny nie jest zgodny z produktem. Sprawdź numer seryjny produktu i spróbuj ponownie. Kliknięcie informacje. aby przejść do strony produktu dla wprowadzonego numeru seryjnego Numer seryjny jest podejrzany według danych Eaton, spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc.
Numer seryjny
Reset Numer seryjny jest podejrzany według danych Eaton, spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Numer seryjny jest nieprawidłowy i nie został rozpoznany przez firmę Eaton. Użyj tego formularza, aby zgłoś ten problem aby uzyskać dalszą pomoc.
Wprowadź 6-cyfrowy kod uwierzytelniania
Wprowadzony produkt jest podejrzany! Spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Wprowadzony kod uwierzytelnienia nie jest zgodny z naszymi danymi dla tego numeru seryjnego. Spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Nieprawidłowy kod uwierzytelnienia. Długość musi wynosić 6 znaków zgłoś ten problem aby uzyskać dalszą pomoc. Kod uwierzytelniający jest wymagany zgłoś ten problem aby uzyskać dalszą pomoc.
Wykonaj wyzwanie Captcha przed uwierzytelnieniem.
Skontaktuj się z nami do zgłoszenia problemu
x
Zgłaszanie problemu
Wprowadź swoje imię i nazwisko.
x
Dziękujemy, Twoje zgłoszenie zostało przyjęte. Nasz zespół produktowy wkrótce się z Tobą skontaktuje.
Uwaga: Jeśli w pobieraniu .zip nie ma pliku(-ów), typ pliku nie jest obsługiwany przez pobieranie zbiorcze.