Bilgi Arama
Belgeyi İndir () / 20
Zor İşler Bizimle Kolay

107666
Model Kodu: NZMB2-S200-BT-CNA

Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 200A, box terminals, B2-S200-BT-CNA

General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker magnetic
Catalog Number
107666
EAN
4015081073320
Product Length/Depth
149 mm
Product Height
195 mm
Product Width
105 mm
Product Weight
2.345 kg
Compliances
RoHS conform
Certifications
UL/CSA
UL (File No. E31593)
UL 489
UL (Category Control Number DKPU2)
IEC 60947-2
IEC/EN 60947
CSA certified
Specially designed for North America
CSA (File No. 22086)
CE marking
CSA-C22.2 No. 5-09
CSA (Class No. 1432-01)
UL listed
IEC
Model Code
NZMB2-S200-BT-CNA

Additional information

Functions
Short-circuit protection

Delivery program

Amperage Rating
200 A
Application
  • Branch circuits, feeder circuits
  • Use in unearthed supply systems at 440 V
Number of poles
Three-pole
Release system
Thermomagnetic release
Special features
  • Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit breaker (Rated short-circuit breaking capacity Icn)
  • Rated current = rated uninterrupted current: 200 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
  • Motor protection in conjunction with contactor and overload relay
  • With short-circuit release
  • Without overload release Ir
Type
Circuit breaker

Design verification as per IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Design verification as per IEC/EN 61439 - technical data

Equipment heat dissipation, current-dependent
38.04 W

Technical Data - Electrical

Amperage Rating
200 A
Direction of incoming supply
As required
Electrical connection type of main circuit
Frame clamp
Isolation
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts)
Lifespan, electrical
7500 operations at 400 V AC-1
6500 operations at 415 V AC-3
Overvoltage category
III
Pollution degree
3
Rated operational current
300 A (415 V AC-1, making and breaking capacity)
300 A (380/400 V AC-1, making and breaking capacity)
200 A (660-690 V AC-3, making and breaking capacity)
Short-circuit total breaktime
< 10 ms
Utilization category
A (IEC/EN 60947-2)
Voltage rating
440 V - 440 V

Technical Data - Mechanical

Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Degree of protection
IP20
IP20 (basic degree of protection, in the operating controls area)
Degree of protection (IP), front side
IP40 (with insulating surround)
IP66 (with door coupling rotary handle)
Degree of protection (terminations)
IP00 (terminations, phase isolator and strip terminal)
IP10 (tunnel terminal)
Lifespan, mechanical
20000 operations
Mounting Method
Fixed
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Special features
  • Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit breaker (Rated short-circuit breaking capacity Icn)
  • Rated current = rated uninterrupted current: 200 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
  • Motor protection in conjunction with contactor and overload relay
  • With short-circuit release
  • Without overload release Ir

Technical Data - Mechanical - Terminals

Terminal capacity (control cable)
14 mm² - 18 mm² (1x)
16 mm² - 18 mm² (2x)
Terminal capacity (copper busbar)
M8 at rear-side screw connection
Min. 16 mm x 5 mm direct at switch rear-side connection
Max. 20 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)
6 mm² - 11 mm² (1x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
6 mm² - 12 mm² (1x) at box terminal
Terminal capacity (copper stranded conductor/cable)
4 mm² - 350 mm² (1x) at box terminal
4 mm² - 3/0 mm² (1x) direct at switch rear-side connection
4 mm² - 350 mm² (1x) at tunnel terminal
Terminal capacity (copper strip)
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 16 mm x 0.8 mm at box terminal

Ürün teknik özelliklerini aktar

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Ürünü Doğrula

16 veya 17 haneli seri numaranızı girin.
Girdiğiniz seri numarası özel karakter içermemelidir. Girdiğiniz seri numarası doğru değil, seri numarası 16 veya 17 haneli olmalıdır. Girdiğiniz seri numarası bulunamadı. Lütfen tekrar deneyin veya Bu sorunu bildir daha fazla destek için. Girdiğiniz seri numarası ürünle eşleşmiyor. Girdiğiniz seri numarası ürünle eşleşmiyor. Tıkla buraya Girdiğiniz seri numarasına ait ürün sayfasına gitmek için… Bu seri numarası Eaton tarafından şüpheli olarak tanımlanmıştır, lütfen tekrar deneyin veya… Bu sorunu bildir daha fazla destek için.
Seri numarası
Sıfırla Bu seri numarası Eaton tarafından şüpheli olarak tanımlanmıştır, lütfen tekrar deneyin veya… Bu sorunu bildir daha fazla destek için. Bu seri numarası Eaton tarafından tanınmıyor ve geçersiz. Lútfen bu formu kullanın Bu sorunu bildir daha fazla destek için.
6 haneli doğrulama kodunu girin.
Girdiğiniz ürün şüpheli görünüyor! Lütfen tekrar deneyin veya Bu sorunu bildir daha fazla destek için. Girdiğiniz doğrulama kodu bu seri numarası için kayıtlarımızla eşleşmiyor. Lütfen tekrar deneyin veya Bu sorunu bildir daha fazla destek için. Geçersiz Doğrulama kodu. Doğrulama kodu 6 haneden oluşmalıdır. Bu sorunu bildir daha fazla destek için. Doğrulama kodu gereklidir Bu sorunu bildir daha fazla destek için.
Doğrulama işleminden önce, Captcha güvenlik doğrulamasını tamamlayın.
Bize Ulaşın Bir sorunu bildirmek için
x
Sorun Bildirin
Lütfen tam adınızı girin.
x
Teşekkür ederiz, talebiniz alındı. Ürün ekibimiz sizinle kısa süre içinde iletişime geçecek.
Not: .zip indirmesinde dosya(lar) eksikse dosya türü toplu indirme tarafından desteklenmiyor demektir.