Codice del modello: FRCMM-63/4/003-U

Eaton Moeller series xEffect - FRCmM Type AC, A, U, R RCCB. Residual current circuit breaker (RCCB), 63A, 4p, 30mA, type U

General specifications

Product Name
Eaton Moeller series xEffect - FRCmM Type AC, A, U, R RCCB
Catalog Number
170455
EAN
4015081669400
Product Length/Depth
80 mm
Product Height
76 mm
Product Width
70 mm
Product Weight
0.368 kg
Compliances
RoHS conform
Certifications
IEC/EN 61008
Model Code
FRCMM-63/4/003-U

Additional information

Features
Additional equipment possible
Residual current circuit breaker
Fitted with:
Interlocking device
Functions
Short-time delayed tripping
Special features
  • Current test marks as per inscription
  • Maximum operating temperature is 75 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.8% for every 1 °C
Used with
FRCmM
Residual current circuit breakers
Type U

Delivery program

Amperage Rating
63 A
Application
Residual current circuit breaker - frequency converter-proof
Fault current rating
30 mA
Impulse withstand current
3 kA (8/20 μs) surge-proof
Number of poles
Four-pole
Rated short-circuit strength
10 kA with back-up fuse
Sensitivity type
Pulse-current sensitive
Tripping time
10 ms delayed
Short time-delayed
Type
  • FRCmM
  • Residual current circuit breakers
  • Type U

Design verification as per IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature - max
75 °C
Ambient operating temperature - min
-25 °C
Equipment heat dissipation, current-dependent
13.4 W
Heat dissipation per pole, current-dependent
3.35 W
Rated operational current for specified heat dissipation (In)
63 A

Technical Data - Electrical

Admissible back-up fuse overload - max
63 A gG/gL
Frequency rating
50 Hz / 60 Hz
50 Hz
Leakage current type
A
Lifespan, electrical
4000 operations
Pollution degree
2
Radiation resistance
Suitable for variable frequency drives (enhanced sensitivity)
Rated fault current - max
0.03 A
Rated fault current - min
0.03 A
Rated impulse withstand voltage (Uimp)
4 kV (1.2/50 µs)
4 kV
Rated insulation voltage (Ui)
440 V
Rated operational voltage (Ue) - max
415 V
Rated residual making and breaking capacity
630 A
Rated short-time withstand current (Icw)
10 kA
Short-circuit rating
63 A (max. admissible back-up fuse)
Surge current capacity
3 kA
Test circuit range
196 V AC - 264 V AC
Voltage rating (IEC/EN 60947-2)
240 V AC / 415 V AC

Technical Data - Mechanical

Built-in depth
70.5 mm
Built-in width (number of units)
70 mm (4 SU)
Busbar material thickness
0.8 mm - 2 mm
Climatic proofing
25-55 °C / 90-95% relative humidity according to IEC 60068-2
Connectable conductor cross section (multi-wired) - max
16 mm²
Connectable conductor cross section (multi-wired) - min
1.5 mm²
Connectable conductor cross section (solid-core) - max
35 mm²
Connectable conductor cross section (solid-core) - min
1.5 mm²
Contact position indicator color
Red / green
Degree of protection
IP20
IP20, IP40 with suitable enclosure
Frame
45 mm
Lifespan, mechanical
20000 operations
Mounting Method
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
DIN rail
Mounting position
As required
Permitted storage and transport temperature - max
60 °C
Permitted storage and transport temperature - min
-35 °C
Status indication
White / blue
Terminal capacity (cable)
M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, PZ2)
Terminal capacity (solid wire)
1.5 mm² - 35 mm²
Terminal capacity (stranded cable)
16 mm² (2x)
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Terminals (top and bottom)
Twin-purpose terminals
Tightening torque
2 Nm - 2.4 Nm
Width in number of modular spacings
4

Esporta le caratteristiche del prodotto

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autentica il prodotto

Inserisci il numero di serie di 16-17 cifre
Il numero di serie inserito non può contenere caratteri speciali. Il numero di serie inserito non è corretto, deve essere di 16 o 17 cifre. Il numero di serie inserito non risulta nei nostri sistemi. Ti preghiamo di riprovare o Segnala questo problema per ulteriore assistenza. Il numero di serie inserito non corrisponde al prodotto. Controlla il numero di serie del prodotto e riprova. Click qui per navigare alla pagina del prodotto corrispondente al numero di serie inserito Il numero di serie risulta sospetto per Eaton; ti preghiamo di riprovare o Segnala questo problema per ulteriore assistenza.
Numero di serie
Reimposta Il numero di serie risulta sospetto per Eaton; ti preghiamo di riprovare o Segnala questo problema per ulteriore assistenza. Il numero di serie non è riconosciuto da Eaton ed è invalido. Utilizza questo modulo per Segnala questo problema per ulteriore assistenza.
Inserisci il codice di autenticazione a 6 cifre
Il prodotto inserito è sospetto! Ti preghiamo di riprovare o Segnala questo problema per ulteriore assistenza. Il codice di autenticazione inserito non corrisponde ai nostri dati per questo numero di serie. Ti preghiamo di riprovare o Segnala questo problema per ulteriore assistenza. Codice di autenticazione non valido. La lunghezza deve essere di 6 caratteri Segnala questo problema per ulteriore assistenza. Il codice di autenticazione è obbligatorio Segnala questo problema per ulteriore assistenza.
Completa la verifica CAPTCHA prima di procedere con l’autenticazione.
Contattaci per segnalare un problema
x
Segnala un problema
Inserisci il tuo nome completo.
x
Grazie, la tua segnalazione è stata inviata. Il nostro team di prodotto ti contatterà a breve.
Nota: Se il formato .zip scaricato presenta dei file mancanti, il loro formato non è supportato per il download.