192467
Kod modelu: NZMH2-MX200-BT-NA

NZMH2-MX200-BT-NA. NZM2 PXR20 circuit breaker, 200A, 3p, box terminal, UL/CSA

General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
192467
EAN
4015081931958
Product Length/Depth
149 mm
Product Height
195 mm
Product Width
105 mm
Product Weight
3.044 kg
Certifications
UL508
CSA (File No. 22086)
CE marking
CSA-C22.2 No. 5-09
UL (File No. E31593)
UL/CSA
Specially designed for North America
UL 489
UL listed
IEC
CSA certified
IEC 60947-2
UL (Category Control Number DIVQ)
CSA (Class No. 1432-01)
Model Code
NZMH2-MX200-BT-NA

Delivery program

Application
Branch circuits, feeder circuits
Type
Circuit breaker
Circuit breaker frame type
NZM2
Number of poles
Three-pole
Amperage Rating
200 A
Release system
Electronic release
Special features
  • Rated current = rated uninterrupted current: 200 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Fitted with:
Thermal protection

Technical Data - Electrical

Voltage rating
690 V - 690 V
Rated operating voltage Ue (UL) - max
480 V
Rated insulation voltage (Ui)
690 V
Amperage Rating
200 A
Instantaneous current setting (Ii) - min
400 A
Instantaneous current setting (Ii) - max
3000 A
Overload current setting (Ir) - min
80 A
Overload current setting (Ir) - max
200 A
Short-circuit release non-delayed setting - min
400 A
Short-circuit release non-delayed setting - max
3000 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
150 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
150 kA
Rated operating power at AC-3, 230 V
55 kW
Rated operating power at AC-3, 400 V
110 kW
Electrical connection type of main circuit
Other
Handle type
Rocker lever
Direction of incoming supply
As required

Technical Data - Mechanical

Mounting Method
Fixed
Built-in device fixed built-in technique
Mounting Method
Fixed
Built-in device fixed built-in technique
Degree of protection
IP20
Special features
  • Rated current = rated uninterrupted current: 200 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
200 A
Equipment heat dissipation, current-dependent
33 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
70 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Functions
Motor protection
Current limiting circuit breaker
Phase failure sensitive

Eksport specyfikacji produktu

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Uwierzytelnianie produktu

Wprowadź swój 16-17-cyfrowy numer seryjny
Wprowadzony numer seryjny nie powinien zawierać znaków specjalnych. Wprowadzony numer seryjny jest nieprawidłowy i powinien składać się z 16 lub 17 cyfr. Wprowadzony numer seryjny nie został znaleziony. Spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Wprowadzony numer seryjny nie jest zgodny z produktem. Sprawdź numer seryjny produktu i spróbuj ponownie. Kliknięcie informacje. aby przejść do strony produktu dla wprowadzonego numeru seryjnego Numer seryjny jest podejrzany według danych Eaton, spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc.
Numer seryjny
Reset Numer seryjny jest podejrzany według danych Eaton, spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Numer seryjny jest nieprawidłowy i nie został rozpoznany przez firmę Eaton. Użyj tego formularza, aby zgłoś ten problem aby uzyskać dalszą pomoc.
Wprowadź 6-cyfrowy kod uwierzytelniania
Wprowadzony produkt jest podejrzany! Spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Wprowadzony kod uwierzytelnienia nie jest zgodny z naszymi danymi dla tego numeru seryjnego. Spróbuj ponownie lub zgłoś ten problem aby uzyskać dalszą pomoc. Nieprawidłowy kod uwierzytelnienia. Długość musi wynosić 6 znaków zgłoś ten problem aby uzyskać dalszą pomoc. Kod uwierzytelniający jest wymagany zgłoś ten problem aby uzyskać dalszą pomoc.
Wykonaj wyzwanie Captcha przed uwierzytelnieniem.
Skontaktuj się z nami do zgłoszenia problemu
x
Zgłaszanie problemu
Wprowadź swoje imię i nazwisko.
x
Dziękujemy, Twoje zgłoszenie zostało przyjęte. Nasz zespół produktowy wkrótce się z Tobą skontaktuje.
Uwaga: Jeśli w pobieraniu .zip nie ma pliku(-ów), typ pliku nie jest obsługiwany przez pobieranie zbiorcze.