Reset
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB. FAZ-RT, 1-pole, tripping characteristic: C, rated current In: 6 A
Product Name |
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB
|
Catalog Number |
102124
|
EAN |
4015081020003
|
Product Length/Depth |
105 mm
|
Product Height |
75.5 mm
|
Product Width |
17.7 mm
|
Product Weight |
0.121 kg
|
Compliances |
RoHS conform
|
Certifications |
CSA (Class No. 1432-01)
UL 489, CSA C22.2 No. 5 IEC/EN 60947-2 Specially designed for North America, suitable as BCPD CSA (File No. 204453) North America (UL listed, CSA certified) CE marking UL (File No. E235139) UL 489 UL (Category Control Number DIVQ) IEC 60947-2 CSA-C22.2 No. 5-09 EN45545-2 IEC 61373 |
Model Code |
FAZ-C6/1-RT
|
Application |
|
Number of poles |
Single-pole
|
Number of poles (total) |
1
|
Number of poles (protected) |
1
|
Tripping characteristic |
C
|
Release characteristic |
C
|
Amperage Rating |
6 A
|
Type |
|
Voltage type |
AC
|
Voltage rating |
277 V AC / 480 V AC
|
Voltage rating at DC |
60 V DC
|
Voltage rating (IEC/EN 60947-2) |
254 V
|
Voltage rating (UL) |
277 V
|
Rated operational voltage (Ue) - max |
240 V
|
Rated insulation voltage (Ui) |
440 V
|
Rated impulse withstand voltage (Uimp) |
4 kV
|
Frequency rating - min |
50 Hz
|
Frequency rating - max |
60 Hz
|
Rated switching capacity (IEC/EN 60947-2) |
15 kA
|
Breaking capacity |
10 kA (UL489)
|
Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V |
0 kA
|
Rated short-circuit breaking capacity (IEC/EN 60898-1)- Icn at 400 V |
0 kA
|
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V |
15 kA
|
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V |
15 kA
|
Selectivity class |
3
|
Overvoltage category |
III
|
Pollution degree |
2
|
Lifespan, electrical |
20000 operations
|
Direction of incoming supply |
As required
|
Frame |
45 mm
|
Enclosure width |
105 mm
|
Width in number of modular spacings |
1
|
Built-in depth |
70.5 mm
|
Mounting width per pole |
17.7 mm
|
Mounting width |
17.7 mm
|
Mounting Method |
Top-hat rail IEC/EN 60715
|
Mounting position |
As required
|
Degree of protection |
IP40 (when fitted)
IP20 (IEC) UL/CSA Type: - IP20 |
Terminals (top and bottom) |
Twin-purpose terminals
|
Connectable conductor cross section (solid-core) - min |
1 mm²
|
Connectable conductor cross section (solid-core) - max |
25 mm²
|
Connectable conductor cross section (multi-wired) - min |
1 mm²
|
Connectable conductor cross section (multi-wired) - max |
25 mm²
|
Terminal protection |
Finger and hand touch safe, DGUV VS3, EN 50274
|
Tightening torque |
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
UL: 4 Nm (36 lb-in) for AWG 6 Max. 2.4 Nm UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8 |
Rated operational current for specified heat dissipation (In) |
6 A
|
Heat dissipation per pole, current-dependent |
0 W
|
Equipment heat dissipation, current-dependent |
1.2 W
|
Static heat dissipation, non-current-dependent |
0 W
|
Heat dissipation capacity |
0 W
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
75 °C
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
Current limiting class |
3
|
Features |
Additional equipment possible
|
Functions |
Current limiting circuit breaker
|
Special features |
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
|
Used with |
Miniature circuit breaker
FAZ-RT |