Eaton Moeller series NZM Earth-fault release, 30mA, 4p, right
| Product Name |
Eaton Moeller series NZM Earth leakage relay
|
| Catalog Number |
104606
|
| EAN |
4015081044160
|
| Product Length/Depth |
220 mm
|
| Product Height |
80 mm
|
| Product Width |
135 mm
|
| Product Weight |
1.6 kg
|
| Compliances |
IEC
RoHS conform |
| Certifications |
IEC/EN 60947-2
IEC/EN 60947-2 annex B |
| Model Code |
NZM1-4-XFI30R
|
| Used with |
N1-4
Four-pole NZM1-4 |
| Voltage rating |
200 - 415 V AC, min. 80 V AC for detection of fault currents type A/AC (dependent on mains voltage)
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Frame |
45 mm
NZM1 |
| Frequency rating |
50 Hz / 60 Hz
|
| Lifespan, mechanical |
20000 operations
|
| Mounting Method |
On the right side
|
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature - min |
-5 °C
|
| Current rating - max |
160 A
|
| Power on-delay time - max |
30 ms
|
| Power on-delay time - min |
30 ms
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
415 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
200 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
415 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
200 V
|
| Rated control supply voltage (Us) at DC - max |
0 V
|
| Current rating - min |
15 A
|
| Degree of protection |
IP20 (operating component area)
|
| Mounting position |
Vertical and 90° in all directions
|
| Fault current detection range |
50/60 Hz
|
| Number of poles |
Four-pole
|
| Terminal capacity (solid/flexible conductor) |
As NZM1 standard terminal without ferrules
As NZM1 standard terminal with ferrules |
| Type |
Accessory
Earth-fault releases
|
| Special features |
Earth-fault release to IEC/EN 60947-2
Not UL/CSA approved
Suitable for use in three-phase systems
Pulse-current sensitive type A according to core-balance principle
For 4 pole NZM1-4 circuit-breakers and N1-4 switch-disconnectors
Supply voltage-dependent Ue = 200 – 415 V 50/60 Hz
Control knobs, sealable.
Fitted on the right side up to In = 160 A at ICu = 50 kA
|
| Application |
In three-phase systems
|
| Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
| Rated control supply voltage (Us) at DC - min |
0 V
|
| Rated fault current - max |
0.03 A
|
| Rated fault current - min |
0.03 A
|
| Rated operating voltage (Ue) - max |
415 V
|
| Sensitivity type |