Vyhledávání znalostí
Stáhnout dokument () z 20
Věci, na kterých záleží, díky nám fungují.

111030
Kód modelu: BPM-O-800/12

Eaton xEnergy Basic LV systems Low voltage switchgear. Surface-mounted installation distribution board with double-bit lock, IP55, HxWxDHxWxD=1260x800x270mm

General specifications

Product Name
Eaton xEnergy Basic small distribution board
Catalog Number
111030
EAN
4015081105915
Product Length/Depth
270 mm
Product Height
1260 mm
Product Width
800 mm
Product Weight
40.3 kg
Compliances
RoHS conform
Model Code
BPM-O-800/12

Portfolio

Type
Basic device
Application
Moisture-proof (installation site)
Color
Light gray (RAL 7035)
Gray

Technické údaje – mechanické

Closure type
Other
Surface finishing
With powder coating
Enclosure material
Steel
Width in number of modular spacings
35
Mounting method
Surface mounted (plaster)
Surface mounting
Material
Sheet steel
Number of rows
7
Built-in depth
300 mm
Built-in height
1290 mm
Built-in width
830 mm
Cover/door model
Closed
Cover/door type
Door
Double-ward lock
Single

Ověření oteplení podle IEC 60890

Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
102 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
204 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
122 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
110 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
244 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
221 W

Ověření návrhu podle ČSN EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP55
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 440 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Další informace

Features
EMC-version
Functions
Basic device
Extension possible
Sealable
RAL-number
7035

Exportovat specifikaci produktu

Poznámka: Pokud v souboru ZIP chybí soubory, pak typ souboru není podporován hromadným stahováním.