Eaton Moeller® series PKE65 System-protective circuit-breaker, Complete device with standard knob, 30 - 65 A, 65 A, With overload release
Product Name |
Eaton Moeller® series PKE System-protective circuit-breaker
|
Catalog Number |
168974
|
EAN |
4015081654659
|
Product Length/Depth |
187 mm
|
Product Height |
162 mm
|
Product Width |
55 mm
|
Product Weight |
1.469 kg
|
Certifications |
IEC/EN 60947
VDE 0660 |
Catalog Notes |
This is a product for Environment A (Industrial). In environment B (household) this device may cause undesirable radio interference. In this case the user may be obliged to take appropriate measures.
|
Model Code |
PKE65/XTUCP-65
|
Actuator type |
Turn button
|
Features |
Complete device with protection unit
|
Fitted with: |
Standard knob
|
Functions |
Line and cable protection
Overload release System protection |
Number of poles |
Three-pole
|
Current flow times - min |
900 (Class 15) AC-4 cycle operation, Main conducting paths
500 (Class 5) AC-4 cycle operation, Main conducting paths For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods. Note: Going below the minimum current flow time can cause overheating of the load (motor). 700 (Class 10) AC-4 cycle operation, Main conducting paths 1000 (Class 20) AC-4 cycle operation, Main conducting paths |
Cut-out periods - min |
≤ 500 ms, main conducting paths, AC-4 cycle operation
|
Degree of protection |
IP20
Terminals: IP00 |
Lifespan, electrical |
50,000 operations (at 400V, AC-3)
|
Lifespan, mechanical |
30,000 Operations (Main conducting paths)
|
Mounting Method |
DIN rail (top hat rail) mounting optional
|
Operating frequency |
60 Operations/h
|
Overload release current setting - min |
30 A
|
Overload release current setting - max |
65 A
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Circuit-breaker PKE
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Suitable for |
DIN rail (top hat rail) mounting
|
Temperature compensation |
-5 - 40 °C to IEC/EN 60947, VDE 0660
-25 - 55 °C, Operating range |
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Terminal capacity (flexible with ferrule) |
2 x (0.75 - 25) mm², ferrule to DIN 46228
1 x (0.75 - 35) mm², ferrule to DIN 46228 |
Terminal capacity (solid) |
2 x (0.75 - 16) mm²
1 x (0.75 - 16) mm² |
Stripping length (main cable) |
14 mm
|
Tightening torque |
1 Nm, Screw terminals, Control circuit cables
3.3 Nm, Screw terminals, Main cable |
Rated frequency - min |
50 Hz
|
Rated frequency - max |
60 Hz
|
Rated operational voltage (Ue) - min |
690 V
|
Rated operational voltage (Ue) - max |
690 V
|
Rated uninterrupted current (Iu) |
65 A
|
Short-circuit release |
Trip block adjustable 5 - 8 x Ir
Basic device fixed 15.5 x Iu, Trip Blocks ± 20% tolerance, Trip blocks Delayed approx. 60 ms, Trip blocks |
Connection |
Screw terminals
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Equipment heat dissipation, current-dependent Pvid |
21.6 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
7.2 W
|
Rated operational current for specified heat dissipation (In) |
65 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|