Vyhledávání znalostí
Stáhnout dokument () z 20
Věci, na kterých záleží, díky nám fungují.

170307
Kód modelu: FRCMM-100/4/03-G/A

Eaton Moeller series xEffect - FRCmM Type AC, A, U, R RCCB. Residual current circuit breaker (RCCB), 100A, 4p, 300mA, type G/A

General specifications

Product Name
Eaton Moeller series xEffect - FRCmM Type AC, A, U, R RCCB
Catalog Number
170307
EAN
4015081668052
Product Length/Depth
76 mm
Product Height
80 mm
Product Width
70 mm
Product Weight
0.381 kg
Compliances
RoHS conform
Certifications
ÖVE E 8601
EN45545-2
IEC 61373
IEC/EN 61008
Model Code
FRCMM-100/4/03-G/A

Additional information

Features
Residual current circuit breaker
Additional equipment possible
Fitted with:
Interlocking device
Functions
Short-time delayed tripping
Special features
  • Current test marks as per inscription
  • Maximum operating temperature is 75 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.2% for every 1 °C
Used with
FRCmM
Residual current circuit breakers
Type G/A (ÖVE E 8601)

Delivery program

Amperage Rating
100 A
Application
  • Switchgear for industrial and advanced commercial applications
  • xEffect - Switchgear for industrial and advanced commercial applications
Fault current rating
300 mA
Impulse withstand current
3 kA (8/20 μs) surge-proof
Number of poles
Four-pole
Rated short-circuit strength
10 kA with back-up fuse
Sensitivity type
Pulse-current sensitive
Tripping time
Short time-delayed
10 ms delayed
Type
  • FRCmM
  • Residual current circuit breakers
  • Type G/A (ÖVE E 8601)

Design verification as per IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Equipment heat dissipation, current-dependent
18.8 W
Heat dissipation capacity
0 W
Heat dissipation per pole, current-dependent
4.7 W
Rated operational current for specified heat dissipation (In)
100 A
Static heat dissipation, non-current-dependent
0 W

Technical Data - Electrical

Admissible back-up fuse overload - max
80 A gG/gL
Frequency rating
50 Hz / 60 Hz
Leakage current type
A
Lifespan, electrical
4000 operations
Pollution degree
2
Rated fault current - max
0.3 A
Rated fault current - min
0.3 A
Rated impulse withstand voltage (Uimp)
4 kV
Rated insulation voltage (Ui)
440 V
Rated operational voltage (Ue) - max
415 V
Rated residual making and breaking capacity
1000 A
Rated short-time withstand current (Icw)
10 kA
Short-circuit rating
100 A (max. admissible back-up fuse)
Surge current capacity
3 kA
Test circuit range
184 V AC - 440 V AC
Voltage rating (IEC/EN 60947-2)
240 V AC / 415 V AC

Technical Data - Mechanical

Built-in depth
70.5 mm
Built-in width (number of units)
70 mm (4 SU)
Busbar material thickness
0.8 mm - 2 mm
Climatic proofing
25-55 °C / 90-95% relative humidity according to IEC 60068-2
Connectable conductor cross section (multi-wired) - max
16 mm²
Connectable conductor cross section (multi-wired) - min
1.5 mm²
Connectable conductor cross section (solid-core) - max
35 mm²
Connectable conductor cross section (solid-core) - min
1.5 mm²
Contact position indicator color
Red / green
Degree of protection
IP20
IP20, IP40 with suitable enclosure
Frame
45 mm
Lifespan, mechanical
20000 operations
Mounting Method
DIN rail
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Mounting position
As required
Permitted storage and transport temperature - max
60 °C
Permitted storage and transport temperature - min
-35 °C
Status indication
White / blue
Terminal capacity (cable)
M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, PZ2)
Terminal capacity (solid wire)
1.5 mm² - 35 mm²
Terminal capacity (stranded cable)
16 mm² (2x)
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Terminals (top and bottom)
Twin-purpose terminals
Tightening torque
2 Nm - 2.4 Nm
Width in number of modular spacings
4

Exportovat specifikaci produktu

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Ověření produktu

Zadejte své 16-17místné sériové číslo
Zadané sériové číslo nesmí obsahovat speciální znaky. Zadané sériové číslo není správné, mělo by mít 16 nebo 17 číslic. Zadané sériové číslo nebylo nalezeno. Zkuste to prosím znovu nebo nahlásit tento problém pro další pomoc. Zadané sériové číslo neodpovídá produktu. Zkontrolujte sériové číslo produktu a zkuste to znovu. Klikněte zde přejít na stránku produktu pro zadané sériové číslo Sériové číslo je společnosti Eaton známo jako podezřelé, zkuste to prosím znovu nebo nahlásit tento problém pro další pomoc.
Sériové číslo
Reset Sériové číslo je společnosti Eaton známo jako podezřelé, zkuste to prosím znovu nebo nahlásit tento problém pro další pomoc. Sériové číslo není společností Eaton rozpoznáno a je neplatné. Tento formulář použijte k nahlásit tento problém pro další pomoc.
Zadejte 6místný ověřovací kód
Produkt, který jste zadali, je podezřelý. Zkuste to prosím znovu nebo nahlásit tento problém pro další pomoc. Zadaný ověřovací kód neodpovídá našim záznamům pro toto sériové číslo. Zkuste to prosím znovu nebo nahlásit tento problém pro další pomoc. Neplatný ověřovací kód. Délka musí být 6 znaků nahlásit tento problém pro další pomoc. Zadejte ověřovací kód nahlásit tento problém pro další pomoc.
Před ověřením dokončete kontrolu Captcha.
Kontaktujte nás nahlásit problém
x
Nahlásit problém
Zadejte celé jméno.
x
Děkujeme, váš dotaz byl odeslán, náš produktový tým vás brzy kontaktuje.
Poznámka: Pokud v souboru ZIP chybí soubory, pak typ souboru není podporován hromadným stahováním.