Eaton Moeller® series CI-K Insulated enclosure, HxWxD=160x100x80mm, +cut-out 45mm CI-K2-80-A
Product Name |
Eaton Moeller® series CI-K Insulated enclosure
|
Catalog Number |
211107
|
EAN |
4015082111076
|
Product Length/Depth |
80 mm
|
Product Height |
180 mm
|
Product Width |
100 mm
|
Product Weight |
0.32 kg
|
Certifications |
IEC 60068-2-11
UL94: HB UL94: VO/1.5 mm thickness IEC/EN 60529 DIN EN 62208 |
Model Code |
CI-K2-80-A
|
Enclosure color |
Light gray, Operator (RAL 7035)
Black (RAL 9005) Light gray, Cover (RAL 7035) |
Enclosure material |
Plastic
1 Ω x 10¹³ (Surface resistance to IEC 60093) |
Features |
UV resistance beneath protective shield
Halogen free |
Fitted with: |
Cover cutout
Push-through cable entry diaphragm Control cable entry |
Knockouts |
Metric cable entry knockouts at the top, bottom and back plate
|
Cover material |
Glass-fiber reinforced polycarbonate
|
Degree of protection |
IP20
NEMA Other |
Dielectric strength |
30 kV/mm, according to IEC 60243-1
|
Flammability characteristics |
960 °C/1 mm thickness (base, cover; glow wire to VDE 0471 Part 2)
650 °C/1 mm thick (push-through membrane and seal material) to VDE 0471 Part 2) |
Model |
Surface mounting
|
Mounting depth |
46 mm
|
Mounting weight capacity - max |
0.7 kg
|
Product category |
Empty enclosures
|
Suitable for |
Emergency stop
|
Surface treatment |
Resistant to corrosion
|
Track resistance |
CTI 175 (cover, to IEC 60112)
CTI 175 (base, to IEC 60112) |
Type |
Basic enclosure
|
Water consumption |
0.29 % (According to DIN EN ISO 62)
|
Environmental resistance |
Not resistant to benzene
Partly resistant to benzene Chemical resistant (Base, Cover) Partly resistant to acids (> 10%) Partly resistant to alcohol Resistant against acids (< 10%) Resistant against alcohol Not resistant to alkalis Resistant against benzene Resistant against alkalis Resistant against gasoline Partly resistant to greases Resistant against salt solutions Resistant against mineral oil Resistant against greases Chemical resistant (Push-through membrane (CI-K1/CI-K2) and sealing material) Not resistant to Mineral oil |
Impact resistance |
IK06 (according to EN 50102)
|
Temperature resistance |
-40 - 80 °C (gasket)
-40 - 120 °C (enclosure) |
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
70 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
10 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire
|
10.2.5 Lifting |
Not applicable.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Meets the product standard's requirements.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|