Eaton Moeller® series CI-K Insulated enclosure, HxWxD=280x200x160mm, +mounting rail, NA type
| Product Name |
Eaton Moeller® series CI-K Insulated enclosure
|
| Catalog Number |
231227
|
| EAN |
4015082312275
|
| Product Length/Depth |
160 mm
|
| Product Height |
280 mm
|
| Product Width |
200 mm
|
| Product Weight |
1.129 kg
|
| Certifications |
CSA File No.: 012528
CSA-C22.2 No. 94 UL CSA UL Category Control No.: MITW2 CSA Class No.: 3211-07 UL 508 IEC/EN 60947-3 CSA-C22.2 No. 14-05 UL File No.: E54120 CE |
| Catalog Notes |
Approved for UL, CSA
|
| Model Code |
CI-K5X-160-TS-NA
|
| Enclosure color |
Black (RAL 9005)
Light gray, Operator (RAL 7035) |
| Enclosure material |
Plastic
|
| Features |
Smooth shape all round with sharp corners
|
| Fitted with: |
DIN-rail
|
| Degree of protection |
NEMA 1
IP65 |
| Degree of protection (front side) |
IP65
|
| Model |
Surface mounting
|
| Mounting depth |
128 mm
|
| Product category |
Basic enclosures
|
| Surface treatment |
Resistant to corrosion
|
| Type |
Basic enclosure
|
| Temperature resistance |
-40 - 80 °C (gasket)
-40 - 120 °C (enclosure) |
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
70 °C
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
41 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire
|
| 10.2.5 Lifting |
Not applicable.
|
| 10.2.6 Mechanical impact |
Meets the product standard's requirements.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Is the panel builder's responsibility.
|
| 10.6 Incorporation of switching devices and components |
Is the panel builder's responsibility.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Meets the product standard's requirements.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|