Stáhnout dokument () z 20
Věci, na kterých záleží, díky nám fungují.

231234
Kód modelu: CI-K5X-125-M-NA

Eaton Moeller® series CI-K Insulated enclosure, HxWxD=280x200x125mm, +mounting plate, NA type

General specifications

Product Name
Eaton Moeller® series CI-K Insulated enclosure
Catalog Number
231234
EAN
4015082312343
Product Length/Depth
125 mm
Product Height
280 mm
Product Width
200 mm
Product Weight
1.403 kg
Certifications
UL
CSA-C22.2 No. 14-05
CSA
CSA-C22.2 No. 94
CSA File No.: 012528
UL File No.: E54120
UL Category Control No.: MITW2
CE
UL 508
IEC/EN 60947-3
CSA Class No.: 3211-07
Catalog Notes
Approved for UL, CSA
Model Code
CI-K5X-125-M-NA

Features & Functions

Enclosure color
Light gray, Operator (RAL 7035)
Black (RAL 9005)
Enclosure material
Plastic
Features
Smooth shape all round with sharp corners
Fitted with:
Mounting plate

General

Degree of protection
NEMA 3R
Indoor and outdoor use
IP65
Degree of protection (front side)
IP65
Model
Surface mounting
Mounting depth
98 mm
Product category
Basic enclosures
Surface treatment
Resistant to corrosion
Type
Basic enclosure

Ambient conditions, mechanical

Temperature resistance
-40 - 120 °C (enclosure)
-40 - 80 °C (gasket)

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Not applicable.
10.2.6 Mechanical impact
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Is the panel builder's responsibility.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Exportovat specifikaci produktu