Bildet er representativt
                                
                                
                                    
                                    Download
                                
                                
                                Eaton EU8E SWD Block module I/O module IP69K, 24 V DC, 8 inputs with power supply, 8 outputs with separate power supply, 8 M12 I/O sockets
| Product Name | 
                                                Eaton EU8E Digital module
                                             | 
| Catalog Number | 
                                                183273
                                             | 
| EAN | 
                                                4015081782062
                                             | 
| Product Length/Depth | 
                                                34 mm
                                             | 
| Product Height | 
                                                212.6 mm
                                             | 
| Product Width | 
                                                61.6 mm
                                             | 
| Product Weight | 
                                                0.32 kg
                                             | 
| Certifications | 
                                                IEC/EN 61131-2  UL CSA | 
| Catalog Notes | 
                                                with supply
                                             | 
| Model Code | 
                                                EU8E-SWD-8D8D-1
                                             | 
| Electric connection type | 
                                                Screw connection
                                             | 
| Features | 
                                                Overload proof (with diagnostics)  Fieldbus connection over separate bus coupler possible Short-circuit protection (sensor supply) Overload protection (sensor supply) | 
| Functions | 
                                                For connection of digital I/O signals  Short-circuit protection, outputs available | 
| Current consumption | 
                                                70 mA, Max. current consumption per M12 I/O plug, Sensor supply, SmartWire-DT network  119 mA, SmartWire-DT network, 24 V, without sensor and without I/O supply | 
| Degree of protection | 
                                                IP69K
                                             | 
| Mounting method | 
                                                Screw fixing (M4)  Wall mounting/direct mounting | 
| Mounting method | 
                                                Screw fixing (M4)  Wall mounting/direct mounting | 
| Overvoltage category | 
                                                II
                                             | 
| Pollution degree | 
                                                3
                                             | 
| Product category | 
                                                SmartWire-DT slave
                                             | 
| Residual ripple | 
                                                ≤ 5 % (input voltage)
                                             | 
| Type | 
                                                Digital modules
                                             | 
| Voltage type | 
                                                DC
                                             | 
| Constant acceleration | 
                                                1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
                                             | 
| Constant amplitude | 
                                                3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
                                             | 
| Drop and topple | 
                                                50 mm Drop height, Drop to IEC/EN 60068-2-31
                                             | 
| Height of fall (IEC/EN 60068-2-32) - max | 
                                                0.3 m
                                             | 
| Mounting position | 
                                                As required
                                             | 
| Shock resistance | 
                                                30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
                                             | 
| Air pressure | 
                                                795 - 1080 hPa (operation)
                                             | 
| Ambient operating temperature - min | 
                                                -25 °C
                                             | 
| Ambient operating temperature - max | 
                                                55 °C
                                             | 
| Ambient storage temperature - min | 
                                                -40 °C
                                             | 
| Ambient storage temperature - max | 
                                                70 °C
                                             | 
| Climatic proofing | 
                                                Damp heat, constant, to IEC 60068-2-3  Dry heat to IEC 60068-2-2 | 
| Environmental conditions | 
                                                Condensation: permissible
                                             | 
| Operating temperature - min | 
                                                -25 °C
                                             | 
| Operating temperature - max | 
                                                55 °C
                                             | 
| Relative humidity | 
                                                5 - 95 % (non-condensing, IEC/EN 60068-2-30)
                                             | 
| Air discharge | 
                                                8 kV, according to IEC 61131-2, level 3, ESD
                                             | 
| Burst impulse | 
                                                2 kV, Supply cable, according to IEC/EN 61131-2, Level 3  1 kV, Signal cable, according to IEC/EN 61131-2, Level 3 1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 | 
| Contact discharge | 
                                                4 kV, according to IEC/EN 61131-2, Level 2, ESD
                                             | 
| Electromagnetic fields | 
                                                3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)  1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008) 10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008) | 
| Radiated RFI | 
                                                10 V (IEC/EN 61131-2:2008, Level 3)
                                             | 
| Radio interference class | 
                                                Class A (EN 55011)
                                             | 
| Surge rating | 
                                                0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC  1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC | 
| Input current | 
                                                4 mA (at 24 V DC, Digital inputs)
                                             | 
| Input current at signal 1 | 
                                                0 mA
                                             | 
| Output current | 
                                                0.5 A
                                             | 
| Power loss | 
                                                3.4 W
                                             | 
| Rated operational voltage | 
                                                24 V DC (-15 %/+ 20 % - power supply)
                                             | 
| Short-circuit tripping current | 
                                                Max. 1.2 A over 3 ms, Digital semi-conductor outputs
                                             | 
| Supply voltage at AC, 50 Hz - min | 
                                                0 VAC
                                             | 
| Supply voltage at AC, 50 Hz - max | 
                                                0 VAC
                                             | 
| Supply voltage at DC - min | 
                                                20.4 VDC
                                             | 
| Supply voltage at DC - max | 
                                                28.8 VDC
                                             | 
| Connection to SmartWire-DT | 
                                                Yes
                                             | 
| Connection type | 
                                                5-pin M12 socket (A-keyed), Supply and I/O sensor  SWD-IN : M12 plug (A-keyed), 5 pole SWD-OUT: M12 socket (A-keyed), 5 pole | 
| Data transfer rate | 
                                                Setting automatically  2 MBit/s, SmartWire-DT | 
| LED indicator | 
                                                Status indication of display outputs: Yellow LED  Status indication of input: Yellow LED Status indication of SmartWire-DT network: Green LED | 
| Protocol | 
                                                Other bus systems
                                             | 
| Station | 
                                                SmartWire-DT slave, SmartWire-DT network
                                             | 
| Input delay | 
                                                < 0.2 ms
                                             | 
| Lamp load | 
                                                ≤ 3 W (at RLL)
                                             | 
| Limit value type 1 | 
                                                High: > 15 V DC  Low: < 5 V DC | 
| Number of inputs (digital) | 
                                                8
                                             | 
| Number of outputs (digital) | 
                                                8
                                             | 
| Output | 
                                                8 Transistor Outputs
                                             | 
| Switching capacity | 
                                                IEC/EN 60947-5-1, utilization category DC-13, Digital outputs
                                             | 
| Explosion safety category for dust | 
                                                None
                                             | 
| Explosion safety category for gas | 
                                                None
                                             | 
| Potential isolation | 
                                                Output to input: yes  Outputs to SmartWire-DT: yes | 
| Protection against polarity reversal | 
                                                Yes
                                             | 
| Equipment heat dissipation, current-dependent Pvid | 
                                                0 W
                                             | 
| Heat dissipation capacity Pdiss | 
                                                0 W
                                             | 
| Heat dissipation per pole, current-dependent Pvid | 
                                                0 W
                                             | 
| Rated operational current for specified heat dissipation (In) | 
                                                0 A
                                             | 
| Static heat dissipation, non-current-dependent Pvs | 
                                                3.4 W
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Meets the product standard's requirements.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Meets the product standard's requirements.
                                             | 
| 10.5 Protection against electric shock | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             |