Eaton's Cooper Power series NOVA-TS triple-single recloser system allows multi-mode configuration for coordinated, precise automation. The system includes three single-phase NOVA-TS reclosers, each with its own manual trip lever and mechanical contact position indicator; one Form 6 triple-single (TS) recloser control; and one compatible, common junction box, including three interconnecting cables to the NOVA-TS reclosers and one receptacle to provide easy access to the Form 6-TS control cable.
Eaton's pad-mounted electronically controlled, enclosed NOVA recloser features solid-dielectric vacuum interruption in a mild steel enclosure design, safeguarding against weather, tampering and rodents.
15-8-400 |
15-12-630 |
15-12-800 |
27-8-400 |
27-12-630 |
27-12-800 |
38-8-400 |
38-12-630 |
38-12-800 |
||
Maximum design voltage (kV) |
15.5 | 15.5 | 15.5 | 27.0 | 27.0 | 27.0 | 38.0 | 38.0 | 38.0 | |
Nominal operating voltage (kV) |
14.4 | 14.4 | 14.4 | 24.9 | 24.9 | 24.9 | 34.5 | 34.5 | 34.5 | |
Basic Insulation Level (BIL**) (kV) |
110 | 110 | 110 | 125 | 125 | 125 | 170 | 170 | 170 | |
60 Hertz withstand voltage (kV) |
Dry, one minute |
50 | 50 | 50 | 60 | 60 | 60 | 70 | 70 | 70 |
Wet, ten seconds |
45 | 45 | 45 | 50 | 50 | 50 | 60 | 60 | 60 | |
Max RIV at 1.0 MHz |
9.4 kV (µV) |
100 | 100 | 100 | – |
– |
– |
– |
– |
– |
16.4 kV (µV) |
– |
– |
– |
100 | 100 | 100 | – |
– |
– |
|
23.0 kV (µV) |
– |
– |
– |
– |
– |
– |
100 | 100 | 100 | |
Continuous current ratings (A) |
400 | 630 | 800 | 400 | 630 | 800 | 400 | 630 | 800 | |
Symmetrical interrupting current (A) |
8000 | 12500* | 12500* | 8000 | 12500* | 12500* | 8000 | 12500 | 12500 | |
Overload capability |
125% - 8 Hours (A) |
500 | 788 | None | 500 | 788 | None | 500 | 788 | None |
150% - 4 Hours (A) |
600 | 945 | – |
600 | 945 | – |
600 | 945 | – |
|
Cable charging current (A) |
10 | 10 | 10 | 25 | 25 | 25 | 40 | 40 | 40 | |
Line charging current (A) |
2 | 2 | 2 | 5 | 5 | 5 | 5 | 5 | 5 | |
Three-second current, Sym. (A) |
8000 | 12500* | 12500* | 8000 | 12500* | 12500* | 8000 | 12500 | 12500 | |
Minimum mechanical/electrical operations without maintenance (C-O) 10,000 | ||||||||||
* 16.0 kA option is also available (Making Current is 40 kA Asymmetrical Peak) |
||||||||||
**Extended BIL option available on 15.5 kV and 27 kV products |
Percent of maximum circuit interrupting rating |
Minimum X/R ratio |
Number of unit operations at 12.5 kA |
Number of unit operations at 16.0 kA |
15-20 | 4 | 88 | 44 |
45-55 | 8 | 112 | 56 |
90-100 | 17 | 32 | 16 |
Total 232 | Total 116 |