Eaton Moeller series Power Defense - Molded Case Circuit Breaker. Circuit-breaker, 3 p, 320A
Product Name |
Eaton Moeller series Power Defense molded case circuit-breaker
|
Catalog Number |
111954
|
EAN |
4015081115020
|
Product Length/Depth |
166 mm
|
Product Height |
275 mm
|
Product Width |
140 mm
|
Product Weight |
5.8 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC/EN 60947
VDE 0660 IEC |
Model Code |
LZMC3-A320-I
|
Amperage Rating |
320 A
|
Voltage rating |
690 V - 690 V
|
Circuit breaker frame type |
LZM3
|
Features |
Protection unit
Motor drive optional |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
3
|
Mounting Method |
Built-in device fixed built-in technique
Fixed |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Equipment heat dissipation, current-dependent |
78.64 W
|
Utilization category |
A (IEC/EN 60947-2)
|
Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
Degree of protection |
In the area of the HMI devices: IP20 (basic protection type)
IP20 |
Direction of incoming supply |
As required
|
Electrical connection type of main circuit |
Screw connection
|
Lifespan, mechanical |
15000 operations
|
Overvoltage category |
III
|
Rated operational current |
500 A (415 V AC-1, making and breaking capacity)
500 A (690 V AC -1, making and breaking capacity) 320 A (660-690 V AC-3, making and breaking capacity) 320 A (415 V AC-3, making and breaking capacity) 500 A (380/400 V AC-1, making and breaking capacity) |
Degree of protection (IP), front side |
IP40 (with insulating surround)
IP66 (with door coupling rotary handle) |
Degree of protection (terminations) |
IP00 (terminations, phase isolator and band terminal)
IP10 (tunnel terminal) |
Number of poles |
Three-pole
|
Lifespan, electrical |
2000 operations at 400 V AC-3
5000 operations at 400 V AC-1 3000 operations at 690 V AC-1 2000 operations at 690 V AC-3 |
Functions |
System and cable protection
|
Type |
Circuit breaker
|
Special features |
|
Application |
Use in unearthed supply systems at 690 V
|
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Position of connection for main current circuit |
Front side
|
Rated operational current for specified heat dissipation (In) |
320 A
|
Release system |
Thermomagnetic release
|
Short-circuit total breaktime |
< 10 ms
|
Rated short-time withstand current (t = 0.3 s) |
3.3 kA
|
Rated short-time withstand current (t = 1 s) |
3.3 kA
|
Short-circuit release non-delayed setting - max |
3200 A
|
Short-circuit release non-delayed setting - min |
1920 A
|
Terminal capacity (copper busbar) |
M10 at rear-side screw connection
|
Terminal capacity (copper solid conductor/cable) |
16 mm² - 185 mm² (1x) at tunnel terminal
|
Handle type |
Rocker lever
|
Short delay current setting (Isd) - max |
0 A
|
Short delay current setting (Isd) - min |
0 A
|
Instantaneous current setting (Ii) - max |
3200 A
|
Instantaneous current setting (Ii) - min |
1920 A
|
Number of operations per hour - max |
60
|
Overload current setting (Ir) - max |
320 A
|
Overload current setting (Ir) - min |
250 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
55 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
36 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
22.5 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz |
9 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
76 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
63 kA
|
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz |
24 kA
|
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
14 kA
|
Standard terminals |
Screw terminal
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
121 kA
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
8000 V
|
Voltage rating (DC) |
750 VDC
|
Rated insulation voltage (Ui) |
1000 V AC
|