Eaton S811 Soft starter, 180 A, 200 - 600 V AC, Us= 24 V DC, with control unit, Frame size T
| Product Name |
Eaton S811 Soft starter
|
| Catalog Number |
168984
|
| EAN |
4015081654697
|
| Product Length/Depth |
164.4 mm
|
| Product Height |
322.9 mm
|
| Product Width |
194.4 mm
|
| Product Weight |
18.6 kg
|
| Certifications |
UL Category Control No.: NMFT
CCC CE UL File No.: E202571 CSA22.2-14-1995 CSA Class No.: 3211-06, 2411-01 GB14048 UL 508 C-Tick CSA IEC/EN 60947-4-2 CSA File No.: LR 353 CSA-C22.2 No. 14 UL |
| Model Code |
S811+T18N3S
|
| Fault memory |
10 Faults
|
| Fitted with: |
Internal bypass contacts
Internal bypass Motor overload protection Display |
| Functions |
Min. ramp time 1 s - fast switching (semiconductor contactor)
Soft start function Underload monitoring Current limitation Potential isolation between power and control sections Suppression of closing transients Suppression of DC components for motors Overload monitoring Single direction |
| Interfaces |
Modbus RTU (built-in)
|
| Class |
Adjustable
|
| Connection to SmartWire-DT |
No
|
| Degree of protection |
IP20
NEMA Other |
| Frame size |
T
|
| Mains voltage - min |
200 V
|
| Mains voltage - max |
600 V
|
| Mounting position |
As required
|
| Overvoltage category |
II
|
| Pollution degree |
3
|
| Radio interference class |
Class A (EN 55011)
|
| Rated impulse withstand voltage (Uimp) |
4000 V
|
| Rated insulation voltage (Ui) |
660 V
|
| Shock resistance |
15 g, Mechanical
|
| Startup class |
CLASS 30 (6 x Iₑ for 30 s)
CLASS 10 (star-delta replacement) CLASS 20 (heavy starting duty 3 x Iₑ for 45 s) |
| Suitable for |
Branch circuits, not as BCPD, (UL/CSA)
|
| Type |
Soft starter for three-phase loads, with control unit
|
| Voltage type |
DC
|
| Altitude |
Max. 2000 m
Above 2000 m with 0.5 % derating per 100 m |
| Ambient operating temperature - min |
-30 °C
|
| Ambient operating temperature - max |
50 °C
|
| Ambient storage temperature - min |
-50 °C
|
| Ambient storage temperature - max |
70 °C
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-3 |
| Overload cycle |
AC-53a: 4.0 - 32: 99 - 3
|
| Rated operational current (Ie) at AC-53 |
180 A
|
| Rated operational current (Ie) at AC-53, in-delta |
311 A
|
| Rated operational voltage (Ue) - min |
200 V
|
| Rated operational voltage (Ue) - max |
600 V
|
| Short-circuit protection rating |
NZMN2-S200, Type “1” coordination, Main conducting paths
|
| Supply frequency |
50/60 Hz, fLN, Main circuit
|
| Voltage rating - max |
600 V
|
| Assigned motor power at 200/208 V, 60 Hz, 3-phase |
60 HP
|
| Assigned motor power at 220/230 V, 60 Hz, 3-phase |
60 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 3-phase |
150 HP
|
| Assigned motor power at 600 V, 60 Hz, 3-phase |
150 HP
|
| Assigned motor power in-delta at 220/230 V, 60 Hz |
100 HP
|
| Assigned motor power in-delta at 460/480 V, 60 Hz |
250 HP
|
| Assigned motor power in-delta at 575/600 V, 60 Hz |
300 HP
|
| Rated operational power at 220/230 V, 50 Hz |
55 kW
|
| Rated operational power at 400 V, 50 Hz |
90 kW
|
| Rated operational power at 500 V, 50 Hz |
110 kW
|
| Rated operational power in-delta at 220/230 V, 50 Hz |
90 kW
|
| Rated operational power in-delta at 400 V, 50 Hz |
160 kW
|
| Rated operational power in-delta at 500 V, 50 Hz |
200 kW
|
| Terminal capacity (flexible with ferrule) |
1 x (2.5 - 4) mm², Control circuit cables
2 x (1 - 2.5) mm², Control circuit cables 2 x (25 - 240) mm², Main cables 1 x (70 - 240) mm², Main cables |
| Terminal capacity (solid) |
2 x (1 - 2.5) mm², Control circuit cables
2 x (25 - 240) mm², Main cables 1 x (70 - 240) mm², Main cables 1 x (2.5 - 4) mm², Control circuit cables |
| Terminal capacity (solid/stranded AWG) |
1 x (14 - 12), Control circuit cables
2 x (4 - 500 kcmil), Main cables 1 x (4 - 500 kcmil), Main cables 2 x (14 - 12), Control circuit cables |
| Terminal capacity (stranded) |
2 x (1 - 2.5) mm², Control circuit cables
1 x (2.5 - 4) mm², Control circuit cables 1 x (70 - 240) mm², Main cables 2 x (25 - 240) mm², Main cables |
| Screwdriver size |
0.6 x 3.5 mm, Terminal screws, Control circuit cables
4 mm Hexagon socket-head screw, Terminal screw, Main cables |
| Tightening torque |
0.4 Nm, Screw terminals, Control circuit cables
25.5 Nm (≤ 150 mm²) 28.3 Nm (> 150 mm²) |
| Current consumption |
150 mA, Control circuit, Digital inputs, External 24 V
10 A/150 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC 1000 mA, Control circuit, Regulator supply 100 mA, Control circuit, Digital inputs, External 24 V (no-load) |
| Drop-out time |
100 ms, DC operated
|
| Drop-out voltage |
0 - 3 V, DC operated
|
| Pick-up time |
100 ms at DC
|
| Pick-up voltage |
21.6 - 26.4 V DC
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
| Rated control supply voltage (Us) at DC - min |
24 V
|
| Rated control supply voltage (Us) at DC - max |
24 V
|
| Input current |
4 - 20 mA (Analog inputs)
|
| Number of inputs |
1 (current input)
|
| Number of outputs |
2 Relay Outputs (programmable)
|
| Output voltage |
120 V AC/DC (relay outputs)
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact
|
| Rated control voltage (Uc) |
24 V DC
24 V DC (-10 %/+10 %) |
| Rated operational current (Ie) at AC-11 |
3 A
|
| Application |
|
| Delay time |
0 - 60 s, Soft start function, Ramp times
|
| Kickstart |
100% (Kickstart voltage)
Max. 2000 ms (Kickstart Duration) |
| Ramp/run-up time |
180 s
|
| Start voltage |
Max. 85 %, Soft start function, Start voltage = turn-off voltage
|
| Equipment heat dissipation, current-dependent Pvid |
25 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
180 A
|
| Static heat dissipation, non-current-dependent Pvs |
25 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|