Eaton SWD4 SWD switch cabinet bushing IP67 to IP20; 5-pole flat cable on 8-pole round cable
Product Name |
Eaton SWD4 Accessory Switch cabinet bushing
|
Catalog Number |
174755
|
EAN |
4015081712410
|
Product Length/Depth |
21 mm
|
Product Height |
82.4 mm
|
Product Width |
35.2 mm
|
Product Weight |
0.05 kg
|
Certifications |
UL File No.: E29184
CSA Class No.: 3211-07 IEC/EN 61131-2 CSA File No.: 2324643 CSA UL UL Category Control No.: NKCR EN 50178 |
Model Code |
SWD4-SML8-12
|
Degree of protection |
IP20
IP20 (according to IEC/EN 60529, EN 50178, VBG 4) |
Overvoltage category |
II
|
Pollution degree |
2
|
Product category |
SmartWire-DT accessories
|
Constant acceleration |
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
Constant amplitude |
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
|
Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
Mounting position |
As required
|
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
Air pressure |
795 - 1080 hPa (operation)
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3 |
Environmental conditions |
Condensation: prevent with appropriate measures
|
Operating temperature - min |
-25 °C
|
Operating temperature - max |
55 °C
|
Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
Electromagnetic fields |
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) 10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008) |
Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
Power loss |
0.6 W
|
Connection type |
Plug, 8-pole
Connection 1: M12 plug (A-keyed), 5 pole |
Number of insertion cycles |
100
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
0.6 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|