Eaton DA1 Variable frequency drive, 500 V AC, 3-phase, 150 A, 110 kW, IP55/NEMA 12, OLED display, DC link choke
Product Name |
Eaton DA1 Variable frequency drive
|
Catalog Number |
176974
|
EAN |
4015081714179
|
Product Length/Depth |
313.5 mm
|
Product Height |
865 mm
|
Product Width |
330 mm
|
Product Weight |
50 kg
|
Certifications |
IEC/EN61800-5
CSA-C22.2 No. 14 DNV Specification for general requirements: IEC/EN 61800-2 UL File No.: E172143 Safety: EN 61800-5-1: 2003 IEC/EN 61800-3 UL report applies to both US and Canada CE RCM CUL UkrSEPRO EAC IEC/EN61800-3 UL Category Control No.: NMMS, NMMS7 Certified by UL for use in Canada RoHS, ISO 9001 UL UL 508C |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Model Code |
DA1-35150NB-B55C
|
Cable length |
150 m, unscreened, maximum permissible, Motor feeder
200 m, screened, with motor choke, maximum permissible, Motor feeder 100 m, screened, maximum permissible, Motor feeder 300 m, unscreened, with motor choke, maximum permissible, Motor feeder |
Communication interface |
EtherCAT, optional
SmartWire-DT, optional CANopen®, built in OP-Bus (RS485), built in DeviceNet, optional Ethernet IP, optional PROFIBUS, optional PROFINET, optional Modbus RTU, built in Modbus-TCP, optional |
Connection to SmartWire-DT |
In conjunction with DX-NET-SWD1 SmartWire DT module
Yes |
Degree of protection |
IP55
NEMA 12 |
Fitted with: |
Additional PCB protection
IGBT inverter OLED display Control unit Brake chopper DC link choke PC connection Internal DC link Breaking resistance |
Frame size |
FS6
|
Functions |
4-quadrant operation possible
|
Mounting position |
Vertical
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
EtherNet/IP
MODBUS Other bus systems PROFIBUS CAN PROFINET IO DeviceNet TCP/IP |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m Max. 1000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
97 % (η)
|
Heat dissipation at current/speed |
1050 W at 100% current and 50% speed
1270 W at 50% current and 90% speed 1660 W at 100% current and 0% speed 2020 W at 100% current and 90% speed 412 W at 25% current and 0% speed 607 W at 25% current and 50% speed 690 W at 50% current and 0% speed 820 W at 50% current and 50% speed |
Input current ILN at 150% overload |
158.4 A
|
Leakage current at ground IPE - max |
150 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
500 V
|
Mains voltage - max |
600 V
|
Operating mode |
Optional: Vector control with feedback (CLV)
Sensorless vector control (SLV) U/f control Speed control with slip compensation |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
500 V AC, 3-phase
600 V AC, 3-phase |
Overload current IL at 150% overload |
225 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) at 150% overload |
150 A
|
Rated operational power at 500 V, 50 Hz, 3-phase |
110 kW
|
Rated operational power at 525 V, 50 Hz, 3-phase |
110 kW
|
Rated operational voltage |
600 V AC, 3-phase
500 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection |
LPJ fuse used together with JM60100-3 fuse base, Power wiring, Assigned switching and protective elements
NH fuse used together with TB00-D fuse base, Power wiring, Assigned switching and protective elements |
Short-circuit protection rating |
200 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), for 4 seconds every 40 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 12 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
600 VAC
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
150 A
|
Assigned motor current IM at 525 V, 50 Hz, 150% overload |
150 A
|
Assigned motor current IM at 550 - 600 V, 60 Hz, 150% overload |
144 A
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
150 HP
|
Apparent power at 600 V |
155.88 kVA
|
Braking resistance |
8 Ω
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit Max. 30 % MN, Standard - Main circuit |
Switch-on threshold for the braking transistor |
975 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
5
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
2
|
Number of relay outputs |
2 (parameterizable, 1 N/O and 1 changeover contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA)
|
Equipment heat dissipation, current-dependent Pvid |
3300 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
150 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Heat dissipation details |
Operation (with 150 % overload)
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|