Foto je ilustrační
Download
Eaton 91PS UPS, 8kVA, 8 kW scalable to 10 kW, 1 string of 9 Ah, Internal Maintenance Bypass
Product Name |
Eaton 91PS and 93PS UPS
|
Catalog Number |
91PS8MBSI
|
EAN |
6430028229482
|
Product Length/Depth |
750 mm
|
Product Height |
950 mm
|
Product Width |
335 mm
|
Product Weight |
158 kg
|
Compliances |
CE Marked
RoHS Compliant CB |
Certifications |
IEC/EN 62040-2
IEC/EN 62040-1 EN 62040-3 Manufactured in a plant certified to ISO 9001 and ISO 14001 management system standards |
Audible alarms |
Yes
|
Auto shutdown function |
Yes
|
Internal battery included |
Yes
|
User replacable batteries |
No
|
Battery charger type |
ABM technology
|
External battery connection |
Hardwired
|
Color |
Black
|
Construction type |
Free standing model
|
Efficiency (eco-mode) |
98 %
|
Improved efficiency mode |
ESS
|
Number of communication slots |
2
|
Feed type |
AC
|
Form factor |
Tower
|
Hot-swappable power modules |
No
|
Input connection |
Fixed connection
|
Number of output connections fixed connection |
1
|
Output frequency |
50 Hz (50/60 Hz programmable)
|
Output power factor |
1
|
Overall efficiency |
96 %
|
Package contents |
|
Parallelable |
Parallel for capacity and redundancy
|
Number of parallel units |
4
|
Phase (input) |
3
|
Phase (output) |
1
|
Potential free switch contact |
Yes
|
Runtime graph |
View runtime graph
|
Snmp |
Yes
|
Start-on-battery |
Yes
|
Topology |
Online
|
Type Of Interface |
Other
|
Internal maintenance bypass |
Yes
|
User Interface (Hmi) |
5 inch touch-screen
|
kVA rating |
8 kVA
|
Wattage |
8 kW
|
Number Of Output Connections With Protective Contact (Schuko) |
0
|
Application |
Data center/ facility/IT
|
Output effective power |
8000 W
|
Transition time for full load |
0 s
|
Efficiency (improved efficiency mode) |
98 %
|
Voltage distortion output (linear load) - max |
1.5 %
|
Integrated functionality |
Network Mangement
|
Input frequency - min |
50 Hz
|
Input frequency - max |
60 Hz
|
Input voltage - min |
220 V
|
Input voltage - max |
415 V
|
Output voltage - min |
220 V
|
Output voltage - max |
240 V
|
Secondary Frequency Min |
50 Hz
|
Secondary Frequency Max |
60 Hz
|
Output apparent power |
8000 VA
|
Primary frequency - max |
60 Hz
|
Primary frequency - min |
50 Hz
|
Runtime at half load |
27 min
|
Runtime at full load |
11 min
|
Mounting Method |
Tower
|