Eaton XT Interference filter for I/O modules of the XC100/200
| Product Name |
Eaton XT Accessory Interference filter
|
| Catalog Number |
118980
|
| EAN |
4015081170975
|
| Product Length/Depth |
90 mm
|
| Product Height |
56.5 mm
|
| Product Width |
35.5 mm
|
| Product Weight |
0.09 kg
|
| Certifications |
IEC/EN 61131-2
EN 50178 |
| Model Code |
XT-FIL-2
|
| Features |
Mains overvoltage protection (power supply)
|
| Connection type |
Screw terminals
|
| Current consumption |
12 A max.
|
| Degree of protection |
IP20
|
| Overvoltage category |
II
|
| Pollution degree |
2
|
| Potential isolation |
Power supply, Input voltage against PE: yes
Power supply, Output voltage against PE: yes |
| Rated impulse withstand voltage (Uimp) |
850 V (auxiliary and control circuits)
|
| Residual ripple |
≤ 5 %
|
| Impact resistance |
500 g/⌀ 50 mm ±25 g
|
| Mounting position |
Horizontal
Vertical |
| Shock resistance |
15 g, Mechanical, Shock duration 11 ms
|
| Vibration resistance |
10 - 57 Hz, ± 0.075 mm
57 - 150 Hz, ± 1.0 g |
| Ambient operating temperature - min |
0 °C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Emitted interference |
Class A (according to DIN/EN 55011/22)
|
| Interference immunity |
According to EN 50082-2
|
| Terminal capacity |
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule, Screw terminals
0.2 - 2.5 mm² (22 - 12 AWG), solid, Screw terminals |
| Supply voltage - max |
28.8 V
|
| Input voltage at DC - min |
20.4 V
|
| Input voltage at DC - max |
24 V
|
| Output current at AC, 50 Hz - max |
12 A
|
| Output voltage at DC - max |
24 V
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|