Eaton Moeller series xPole - mRB4/6 RCBO - residual-current circuit breaker with overcurrent protection. RCD/MCB, 6A, 30mA, C-LS-Char, 3N pole, FI-Char: A
Product Name |
Eaton Moeller series xPole - mRB4/6 RCBO - residual-current circuit breaker with overcurrent protection
|
Catalog Number |
120657
|
EAN |
4015081184873
|
Product Length/Depth |
80 mm
|
Product Height |
75.5 mm
|
Product Width |
70 mm
|
Product Weight |
0.445 kg
|
Compliances |
CE Marked
RoHS conform |
Certifications |
CE
|
Model Code |
mRB6-6/3N/C/003-A
|
Voltage rating |
400 V
|
Surge current capacity |
0.25 kA
|
Voltage type |
AC
|
Width in number of modular spacings |
4
|
Features |
Concurrently switching N-neutral
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
Device height |
80 mm
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Mounting style |
Tri-stable slide catch - enables removal from existing busbar combination
|
Operating ambient temperature - max |
40 °C
|
Operating ambient temperature - min |
-25 °C
|
Product application |
Switchgear for industrial and advanced commercial applications
|
Product range |
mRB6
|
Rated current |
6 A
|
Rated current of product range |
6 - 25 Ampere
|
Rated fault currents of product range |
30, 100, 300 MilliAmpere
|
Rated operational current for specified heat dissipation (In) |
6 A
|
Rated switching capacity (IEC/EN 60947-2) |
6 kA
|
Rated switching capacity (IEC/EN 61009) |
6 kA
|
Static heat dissipation, non-current-dependent |
0 W
|
Tripping characteristic |
C
|
Built-in depth |
70 mm
|
Current limiting class |
3
|
Rated short-circuit breaking capacity (EN 60947-2) |
0 kA
|
Frame |
45 mm
|
Terminal protection |
Busbar tag shroud to VBG4
|
Terminals (top and bottom) |
Twin-purpose
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-25 °C
|
Fault current rating |
0.03 A
|
Heat dissipation capacity |
0 W
|
Heat dissipation per pole, current-dependent |
0 W
|
Number of poles (protected) |
4
|
Number of poles (total) |
4
|
Rated operational voltage (Ue) - max |
400 V
|
Rated short-circuit breaking capacity (IEC 60947-2) |
0 kA
|
Rated switching capacity |
6 kA
|
Back-up fuse |
100 Ampere gL
|
Basic function |
Combined RCD/MCB devices
|
Mounting Method |
DIN rail
|
Climatic proofing |
IEC 68-2: 25 °C - 55 °C at 90 % - 95 % humidity
|
Equipment heat dissipation, current-dependent |
4.8 W
|
Rated impulse withstand voltage (Uimp) |
4 kV
|
Degree of protection (built in) |
IP40
|
Degree of protection |
IP20
|
Operating ambient temperature hint |
Keep in mind the derating at temperatures higher than 40 °C
|
Solid terminal capacities |
1 - 25 Square Millimeter
|
Standards |
IEC/EN 61009
|
Tripping |
Non-delayed
|
Overvoltage category |
III
|
Pollution degree |
2
|
Material thickness |
2 mm
|
Rated non-tripping current |
0.5 x I∆n
|
Impulse withstand current |
Partly surge-proof, 250 A
|
Leakage current type |
A
|
Release characteristic |
C
|
Sensitivity type |
Type A, pulse-current sensitive
|
Frequency rating |
50 Hz
|
Rated insulation voltage (Ui) |
500 V
|
Connectable conductor cross section (solid-core) - min |
1 mm²
|
Connectable conductor cross section (solid-core) - max |
25 mm²
|
Connectable conductor cross section (multi-wired) - min |
1 mm²
|
Connectable conductor cross section (multi-wired) - max |
25 mm²
|
Rated short-circuit breaking capacity (EN 61009) |
6 kA
|
Rated short-circuit breaking capacity (EN 61009-1) |
6 kA
|
Voltage rating at AC |
230 V / 400 V
|
Number of poles |
Three-pole + N
|
Disconnection characteristic |
Undelayed
|
Type |
RCBO
|
Application |
Switchgear for residential and commercial applications
|
Selectivity class |
3
|