Ladda ner dokument () av 20

144064
Modellkod: EU5E-SWD-4PT

Eaton EU5E I/O module, SmartWire-DT, 24 V DC, 4AI configurable Pt100 / Pt1000: -50 - +200°C, Ni1000: -50 - +150 °C

General specifications

Product Name
Eaton EU5E Accessory Input module
Catalog Number
144064
EAN
4015081405947
Product Length/Depth
102 mm
Product Height
90 mm
Product Width
35 mm
Product Weight
0.092 kg
Certifications
UL File No.: E29184
UL Category Control No.: NKCR
IEC/EN 61131-2
CSA Class No.: 3211-07
UL
CSA
CSA File No.: 2324643
Model Code
EU5E-SWD-4PT

Особенности и & функции

Electric connection type
Flat plug-in connection
Features
Input, resistance thermometer
Analog outputs configurable
Fieldbus connection over separate bus coupler possible
Analog inputs configurable
Fitted with:
Display mode for temperatures (°C, °F, raw value)
Temperature sensors PT100, PT1000 and Ni1000
Functions
For connection of analog I/O signals
Adjustable parameter settings

Общие сведения

Current consumption
22 mA, SmartWire-DT network
Degree of protection
IP20
NEMA 1
Mounting method
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Rail mounting possible
Wall mounting/direct mounting
Overvoltage category
II
Pollution degree
2
Product category
SmartWire-DT slave
Repetition accuracy
0.5 % (Temperature inputs)
Residual ripple
≤ 5 % (input voltage)
Terminal capacity
0.25 - 1.5 mm² (24 - 16 AWG), flexible with ferrule, Terminal for I/O sensor
0.2 - 1.5 mm² (AWG 24 - 16), solid, Terminal for I/O sensor
Type
Analog modules
Voltage type
DC

Условия окружающей среды, механические характеристики

Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
As required
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts

Климатические условия окружающей среды

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2
Environmental conditions
Condensation: prevent with appropriate measures
Operating temperature - min
-50 °C
Operating temperature - max
55 °C
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)

Электромагнитная совместимость

Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse
2 kV, Signal cable, according to IEC/EN 61131-2, Level 3
2 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference class
Class B (EN 55011)
Surge rating
1 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC

Расчетные электрические характеристики

Power loss
0.6 W
Rated operational voltage
24 V DC (-15 %/+ 20 % - power supply)
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
0 VDC
Supply voltage at DC - max
0 VDC

Связь

Connection to SmartWire-DT
Yes
Connection type
Plug, 8-pole, SmartWire-DT
Push in terminals, Supply and I/O sensor
Connection plug: external device plug SWD4-8SF2-5, SmartWire-DT
Data transfer rate
Setting automatically
250 kBit/s, SmartWire-DT
LED indicator
Status indication of SmartWire-DT network: Green LED
Protocol
Other bus systems
Station
SmartWire-DT slave, SmartWire-DT network

Ввод / вывод

Conversions
250 ms, Temperature inputs
Input
Inputs, configurable (PT100, PT1000, Ni1000)
Number of inputs (analog)
4
Number of outputs (analog)
0
Resolution
0.1 °C, Temperature inputs
Total error
± 1 %, Temperature Inputs

Безопасность

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Inputs for SmartWire-DT: yes
Protection against polarity reversal
Yes, for supply voltage (Siemens MPI optional)
Yes

Отчеты о верификации проекта (DVs)

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0.6 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Exportera produktspecifikationer