Eaton Moeller® series PKE Function element for connecting interface to SmartWire-DT
Product Name |
Eaton Moeller® series PKE Function element
|
Catalog Number |
172735
|
EAN |
4015081692811
|
Product Length/Depth |
75 mm
|
Product Height |
65 mm
|
Product Width |
67.5 mm
|
Product Weight |
0.028 kg
|
Certifications |
IEC/EN 61131-2
|
Model Code |
PKE-SWD-CP
|
Functions |
Remote circuit-breaker de-energization
For attachment to PKE circuit-breakers Display of Set short-circuit release value Display of Contactor state PKE Display of Trip indications (Overload, Short-circuit,...) Display of Part no. of trip block Display of All phase currents in % For connecting the PKE circuit-breaker with PKE-XTU(W)ACP-... trip blocks to SmartWire-DT Display of Thermal load as a % System protection Display of Set value of overload releases |
Accessory/spare part type |
Communication and measuring function
|
Current consumption |
35 mA, SmartWire-DT network, 15-V-SWD supply
|
Degree of protection |
IP20
|
Overvoltage category |
II
|
Pollution degree |
2
|
Product category |
|
Type |
Function element
|
Constant acceleration |
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
Constant amplitude |
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
|
Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
Mounting position |
As PKE32/65
|
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient storage temperature - min |
-30 °C
|
Ambient storage temperature - max |
70 °C
|
Environmental conditions |
Condensation: prevent with appropriate measures
|
Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
Burst impulse |
1 kV, SmartWire-DT cable, Signal cable, according to IEC/EN 61131-2, Level 3
1 kV, CAN/DP-bus cable, SmartWire-DT cables, according to IEC/EN 61131-2, Level 3 |
Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
Electromagnetic fields |
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008) 3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) |
Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
Radio interference class |
Class A (EN 55011)
|
Addressing |
Address set automatically
|
Connection to SmartWire-DT |
Yes
|
Connection type |
SWD: Plug, 8-pole
External device plug SWD4-8SF2-5, SmartWire-DT |
LED indicator |
Status indication of SmartWire-DT network: Green LED
|
Station |
SmartWire-DT slave, SmartWire-DT network
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|