Eaton XN-322 Analog input module, 4 analog inputs, Pt/Ni/KTY/R with 2-wire or 3-wire connection
| Product Name |
Eaton XN-322 Input module
|
| Catalog Number |
178772
|
| EAN |
7640130098367
|
| Product Length/Depth |
104.2 mm
|
| Product Height |
16.8 mm
|
| Product Width |
80.3 mm
|
| Product Weight |
0.056 kg
|
| Certifications |
CE
UL File No.: E135462 cULus EN 61131-2 EN 61000-6-2 EN 61000-6-4 UL508 CSA-C22.2 No. 142-M |
| Model Code |
XN-322-4AI-PTNI
|
| Electric connection type |
Plug-in connection
|
| Features |
Input, resistance thermometer
Fieldbus connection over separate bus coupler possible Analog outputs configurable Input, resistor Analog inputs configurable Input signal, configurable |
| Fitted with: |
10 kHz, second-order low-pass input filter
Parameterizable Software input filter |
| Measurement ranges |
0 - 1000 (Resistance measurement)
0 - 2500 (Resistance measurement) -40 - 300 °C (Temperature measurement, KTY84) 0 - 500 (Resistance measurement) -50 - 150 °C (Temperature measurement, KTY11) -200 - 850 °C (Temperature measurement, PT100/200/500/1000) -60 - 250 °C (Temperature measurement, NI100/1000) -60 - 150 °C (Temperature measurement, NI100/1000) 0 - 250 (Resistance measurement) 0 - 5000 (Resistance measurement) -200 - 150 °C (Temperature measurement, PT100/200/500/1000) -55 - 150 °C (Temperature measurement, KTY81) |
| Value representation |
SIGNED16 (0.1 °C), UNSIGNED16 (0.1 Ω), Temperature and resistance measurement
|
| Current consumption |
37 mA (typ.), for +24 V, Power supply - Input
0 mA (typ.), for +5 V power supply (internal), Power supply - Input |
| Degree of protection |
IP20
NEMA 1 |
| Mounting method |
Rail mounting possible
|
| Number of channels |
4, Analog Inputs
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Product category |
XN-322 analog input module
|
| Resolution |
16 Bit (Analog inputs)
|
| Type |
|
| Used with |
XN-312-…
XN300 |
| Voltage type |
DC
|
| Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
| Mounting position |
Horizontal
|
| Shock resistance |
15 g, Mechanical, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Vibration resistance |
5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Ambient operating temperature - min |
0 °C
|
| Ambient operating temperature - max |
60 °C
|
| Ambient storage temperature - min |
-20 °C
|
| Ambient storage temperature - max |
85 °C
|
| Climatic proofing |
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3 |
| Environmental conditions |
Condensation: prevent with appropriate measures
|
| Relative humidity |
0 - 95 % (non-condensing)
|
| Air discharge |
8 kV
|
| Burst impulse |
1 kV, Signal cable
2 kV, Supply cable |
| Contact discharge |
4 kV
|
| Electromagnetic fields |
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
| Emitted interference |
47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency)
40 dB (at 30 - 230 MHz, Class A, radiated, high frequency) |
| Radiated RFI |
10 V
|
| Surge rating |
0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC
1 kV, Signal cable, unbalanced, EMC |
| Voltage dips |
Voltage dips: 10 ms/Voltage fluctuations: Yes
|
| Terminal capacity |
0.2 - 1.5 mm², flexible without ferrule, H07V-K
0.2 - 1.5 mm², solid, H07V-U 24 - 16 AWG 0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) 0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) |
| Gauge pin |
A1 (according to IEC/EN 60947-1)
|
| Stripping length (main cable) |
10 mm
|
| Insulating material group |
I
|
| Rated operational voltage |
160 V (terminations)
|
| Supply voltage at AC, 50 Hz - min |
0 VAC
|
| Supply voltage at AC, 50 Hz - max |
0 VAC
|
| Supply voltage at DC - min |
18 VDC
|
| Supply voltage at DC - max |
30 VDC
|
| Connection type |
2-conductor/3-conductor, Temperature and resistance measurement
Push-in spring-cage terminal (plug-in connection), Connection design in TOP direction |
| Protocol |
Other bus systems
|
| Accuracy |
± 0.3 % of full scale, Temperature and resistance measurement
|
| Input |
4 Analog resistance inputs (Pt/Ni/KTY/R with 2-wire or 3-wire connection)
|
| Load current |
Not specified by plug manufacturer
|
| Measured variables |
Temperature
Resistance |
| Number of inputs (analog) |
4
|
| Number of outputs (analog) |
0
|
| Value refresh time/cycle time |
Min. 4 / 4 ms (per channel / all channels), Analog Inputs
|
| Explosion safety category for dust |
None
|
| Explosion safety category for gas |
None
|
| Potential isolation |
Analog inputs: no
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0.768 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
1.08 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|