Ladda ner dokument () av 20

184784
Modellkod: EMR6-VM600-A-1

Eaton Moeller® series EMR6 Voltage monitoring relay, 3 - 30, 5 - 60, 30 - 300, 60 - 600 V, 24 - 240 V AC, 50/60 Hz, 24 - 240 V DC

General specifications

Product Name
Eaton Moeller® series EMR6 Voltage monitoring relay
Catalog Number
184784
EAN
4015081788200
Product Length/Depth
103.7 mm
Product Height
85.6 mm
Product Width
22.5 mm
Product Weight
0.154 kg
Certifications
UL508
EAC
RMRS
CCC
RCM
CSA-C22.2 No. 14
GL
Model Code
EMR6-VM600-A-1

Merkmale und Funktionen

Electric connection type
Screw connection
Functions
Single-phase under voltage possible
DC-under voltage
Single-phase over voltage possible
DC-over voltage
Monitoring function
Undervoltage
Overvoltage
Voltage measurement - min
3 V
Voltage measurement - max
600 V

Allgemein

Degree of protection
Enclosure: IP50
Terminals: IP20
Lifespan, mechanical
30,000,000 Operations
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product Category
EMR Measuring and monitoring relays
Rated impulse withstand voltage (Uimp)
4000 V AC
Shock resistance
Class 2
LED indicator
Status indication of energized output relay: Yellow LED
Status indication of Supply voltage: Yellow LED
Status indication of errors: Red LED
Other states depending on fault (see IL): Measured value
Status indication of Supply voltage: Green, solid light
Type
Voltage monitor
Voltage type
AC/DC
Voltage type
AC/DC

Klimatische Umweltbedingungen

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
85 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30

Elektromagnetische Verträglichkeit

Air discharge
Air/contact discharge, according to IEC/EN 61000-4-2, level 3
Burst impulse
According to IEC/EN 61000-4-4, level 3
Electromagnetic compatibility
According to IEC/EN 60947-6-2
Immunity to line-conducted interference
Level 3 (according to IEC/EN 61000-4-6)
Immunity to radiation
Level 3 (according to IEC/EN 61000-4-3)
Surge rating
According to IEC/EN 61000-4-5 Level 4

Anschlussquerschnitte

Connection type
Snap fixing, top-hat rail IEC/EN 60715
Terminal capacity (flexible with ferrule)
2 x 0.5-1.5 mm²
Terminal capacity (flexible with ferrule AWG)
2 x 18-16
Terminal capacity (solid)
1 x 0.5-2.5 mm²
Terminal capacity (solid AWG)
18 - 14
Screwdriver size
5.5 x 0.8 mm, Terminal screw
Tightening torque
Min. 0.5 Nm, Screw terminals
0.8 Nm, Screw terminals

Zeitzyklus

Delay time
Adjustable from 0.1 - 30 s, Response delay time
Timing cycle
Adjustable from 0.1 – 30 s, Reset delay/Off-delay time

Stromversorgung

Duty factor
100 %, Power supply
Power consumption
2.6 VA
Rated control supply voltage (Us) at AC, 50 Hz - min
24 V
Rated control supply voltage (Us) at AC, 50 Hz - max
240 V
Rated control supply voltage (Us) at AC, 60 Hz - min
24 V
Rated control supply voltage (Us) at AC, 60 Hz - max
240 V
Rated control supply voltage (Us) at DC - min
24 V
Rated control supply voltage (Us) at DC - max
240 V
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Supply voltage
24 - 240 V AC, 50/60 Hz
24 - 240 V DC
Voltage tolerance
0.85 x Uc
1.1 x Uc

Messstromkreise

Connection type
Snap fixing, top-hat rail IEC/EN 60715
Hysteresis
3 - 30 %
Threshold value
3 V AC, Min. undervoltage response value
3 V AC, Min. overvoltage response value
600 V AC, Max. undervoltage response value
600 V AC, Max. overvoltage response value

Relais-Ausgangskontakte

Number of contacts (change-over contacts)
2
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0
Lifespan, electrical
100,000 Operation (at 230 V, AC-12, 4 A)

Exportera produktspecifikationer

Observera: Om fil(er) saknas från .zip nedladdningen stöds filtypen inte av massnedladdning.