Eaton easyPOW Power supply unit, 100-240VAC/24VDC/12VDC, 0.35A/0.02A, 1-phase, controlled
Product Name |
Eaton easyPOW power supply unit
|
Catalog Number |
229424
|
EL Number |
4515006
|
EAN |
4015082294243
|
Product Length/Depth |
58 mm
|
Product Height |
90 mm
|
Product Width |
36 mm
|
Product Weight |
0.085 kg
|
Certifications |
CE
UL Category Control No.: NRAQ CSA-C22.2 No. 213-M1987 IEC 60068-2-27 UL File No.: E135462 EN 55022 CSA Class No.: 2252-01 + 2258-02 CSA File No.: 012528 CSA UL IEC 60068-2-6 EN 55011 IEC/EN 61000-4 CSA-C22.2 No. 142-M1987 UL 508 |
Model Code |
EASY200-POW
|
Features |
Overload proof (by current limitation)
Proof against sustained short circuit, hickup mode (Output current 24 V DC) |
Number of phases |
1
|
Degree of Protection |
IP20 (according to IEC/EN 60529, EN 50178, VBG 4)
|
Mounting Method |
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) |
Product category |
Control relays easyE4
|
Used with |
easyE4
|
LED indicator |
Status Indication of 24 V DC output voltage: Continuous green light LED
|
Power consumption |
7 W typ.
|
Mounting position |
Vertical
Horizontal |
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
Altitude |
Max. 2000 m
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
40 °C
|
Ambient storage temperature - max |
70 °C
|
Air discharge |
8 kV, according to IEC/EN 61000-4-2, Level 3, ESD
|
Burst impulse |
2 kV, according to IEC/EN 61000-4-4, Level 3
|
Contact discharge |
6 kV, according to IEC/EN 61000-4-2, Level 3, ESD
|
Electromagnetic fields |
10 V/m (according to IEC EN 61000-4-3)
|
Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
Surge rating |
6 kV, Surge voltage (EN 50178), 24 V, EMV
2 kV, Supply cables, symmetrical, power pulses (Surge), EMC 0.5kV, outgoer cables symmetrical, EASY…DC, IEC/EN 61000-4-5, level 2, 24 V EMC |
Terminal capacity (flexible with ferrule) |
0.2/2.5 mm²
|
Terminal capacity (flexible with ferrule AWG) |
22 - 12
|
Terminal capacity (solid) |
0.2/4 mm²
|
Terminal capacity (solid AWG) |
22 - 12
|
Tightening torque |
0.6 Nm, Screw terminals
|
Protection class |
2 (IEC/EN 60536)
|
Current limitation |
20 mA, effectiveness of current limitation, 12 V DC (reference voltage), output current
0.4 A, effectiveness of current limitation, 24 V DC, output current |
Insulation resistance |
According to EN 50178
|
Potential isolation |
SELV (VDE 0100 Part 410; IEC 60364-4-41, HD 384.4.41 S2) EN 60950, EN 50178 (primary/secondary)
|
Input current at AC - max |
0.17 A
|
Input voltage at AC 50 Hz - min |
85 V
|
Input voltage at AC 50 Hz - max |
264 V
|
Input voltage at DC - min |
0 V
|
Input voltage at DC - max |
0 V
|
Inrush current |
5 A (at 25 °C, 230 V)
|
Mains failure bridging |
> 10 ms (at 115 V, according to IEC/EN 61000-4-11)
> 20 ms (at 230 V, according to IEC/EN 61000-4-11) |
Efficiency |
80 %
|
Output current at AC, 50 Hz - max |
0.35 A
|
Output voltage |
± 1 % (Effect with 25 - 100 % load change)
± 1 % (Effect of input voltage) |
Output voltage at AC 50 Hz - max |
12 V
|
Output voltage at DC - min |
12 V
|
Output voltage at DC - max |
24 V
|
Rated output power |
10 W
|
Short-circuit protection |
Yes, Proof against sustained short circuit, 12 V DC (reference voltage), Output current
|
Voltage tolerance |
± 4 %, Rated output voltage 12 V DC
± 3 %, Rated output voltage 24 V DC |
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
1 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|