Eaton DA1 Frequency inverter, 230 V AC, 3-phase, 72 A, 18.5 kW, IP20/NEMA 0, Radio interference suppression filter, Additional PCB protection, DC link choke, FS5
Product Name |
Eaton DA1 Variable frequency drive
|
Catalog Number |
197491
|
EAN |
4015081940660
|
Product Length/Depth |
261 mm
|
Product Height |
485 mm
|
Product Width |
234 mm
|
Product Weight |
18.2 kg
|
Certifications |
CE
EAC IEC/EN 61800-3 UL report applies to both US and Canada IEC/EN61800-3 UkrSEPRO CUL RCM IEC/EN 61800-2 UL File No.: E172143 UL Certified by UL for use in Canada Safety: EN 61800-5-1: 2003 RoHS, ISO 9001 IEC/EN61800-5 UL 508C UL Category Control No.: NMMS, NMMS7 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Model Code |
DA1-32072FB-B20C
|
Cable length |
C2 ≤ 5 m, maximum motor cable length
150 m, unscreened, maximum permissible cable length 200 m, unscreened, with motor choke, maximum permissible cable length 200 m, screened, with motor choke, maximum permissible cable length C3 ≤ 25 m, maximum motor cable length 100 m, screened, maximum permissible cable length |
Communication interface |
Modbus RTU
CANopen® SmartWire-DT, optional Ethernet IP, optional OP-Bus (RS485) PROFINET, optional EtherCAT, optional DeviceNet, optional PROFIBUS, optional Modbus-TCP, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DX-NET-SWD1 SmartWire DT module |
Degree of protection |
IP20
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Fitted with: |
Radio interference suppression filter
OLED display PC connection IGBT inverter Brake chopper DC link choke Internal DC link Additional PCB protection Control unit Breaking resistance |
Frame size |
FS5
|
Functions |
4-quadrant operation possible
|
Mounting position |
Vertical
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
PROFINET IO
Other bus systems EtherNet/IP MODBUS CAN TCP/IP PROFIBUS DeviceNet |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Suitable for |
Branch circuits, (UL/CSA)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m Max. 1000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
95.8 % (η)
|
Heat dissipation at current/speed |
200 W at 25% current and 0% speed
260 W at 25% current and 50% speed 280 W at 50% current and 0% speed 370 W at 50% current and 50% speed 510 W at 50% current and 90% speed 650 W at 100% current and 0% speed 760 W at 100% current and 50% speed 870 W at 100% current and 90% speed |
Input current ILN at 150% overload |
82.9 A
|
Leakage current at ground IPE - max |
0.28 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
200 V
|
Mains voltage - max |
240 V
|
Operating mode |
U/f control
Sensorless vector control (SLV) Optional: Vector control with feedback (CLV) Speed control with slip compensation |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
240 V AC, 3-phase
230 V AC, 3-phase |
Overload current IL at 150% overload |
105 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) at 150% overload |
72 A
|
Rated operational power at 220/230 V, 50 Hz, 1-phase |
18.5 kW
|
Rated operational voltage |
240 V AC, 3-phase
230 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Starting current - max |
200 %, IH, max. starting current (High Overload), for 4 seconds every 40 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
240 VAC
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
68 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
72 A
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
25 HP
|
Apparent power at 230 V |
28.68 kVA
|
Apparent power at 240 V |
29.93 kVA
|
Braking resistance |
12 Ω
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Adjustable to 100 % (DC) Max. 30 % MN, Standard - Main circuit |
Switch-on threshold for the braking transistor |
390 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
5
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
2
|
Number of relay outputs |
2 (parameterizable, 1 N/O and 1 changeover contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA)
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|