Eaton Moeller® series Rapid Link - Speed controllers, 4.3 A, 1.5 kW, Sensor input 4, AS-Interface®, S-7.4 for 31 modules, HAN Q4/2, with manual override switch, with braking resistance
Product Name |
Eaton Rapid Link Speed controller
|
Catalog Number |
198784
|
EAN |
4015081968428
|
Product Length/Depth |
157 mm
|
Product Height |
270 mm
|
Product Width |
220 mm
|
Product Weight |
3.59 kg
|
Certifications |
CE
UL approval RoHS UL 61800-5-1 IEC/EN 61800-5-1 |
Catalog Notes |
|
Model Code |
RASP5-4400A31-412R100S1
|
Features |
Parameterization: Fieldbus
Parameterization: Keypad Parameterization: drivesConnect Diagnostics and reset on device and via AS-Interface Parameterization: drivesConnect mobile (App) |
Fitted with: |
Thermo-click with safe isolation
Key switch position OFF/RESET Braking resistance PC connection Manual override switch Key switch position HAND Internal DC link Breaking resistance IGBT inverter Selector switch (Positions: REV - OFF - FWD) Control unit Key switch position AUTO Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation PTC thermistor monitoring |
Functions |
Brake chopper with braking resistance for dynamic braking
1 potentiometer speed 4-quadrant operation possible 3 fixed speeds |
Degree of protection |
NEMA 12
IP65 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Overvoltage category |
III
|
Product category |
Speed controller
|
Protocol |
AS-Interface profile cable: S-7.4 for 31 modules
ASI |
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: for conducted emissions only |
Rated impulse withstand voltage (Uimp) |
2000 V
|
System configuration type |
AC voltage
Center-point earthed star network (TN-S network) Phase-earthed AC supply systems are not permitted. |
Mounting position |
Vertical
|
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms, Half-sinusoidal shock 11 ms, 1000 shocks per shaft
|
Vibration |
Resistance: 57 Hz, Amplitude transition frequency on acceleration
Resistance: 6 Hz, Amplitude 0.15 mm Resistance: According to IEC/EN 60068-2-6 Resistance: 10 - 150 Hz, Oscillation frequency |
Altitude |
Above 1000 m with 1 % performance reduction per 100 m
Max. 2000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
In accordance with IEC/EN 50178
< 95 %, no condensation |
Current limitation |
Adjustable, motor, main circuit
0.4 - 4.3 A, motor, main circuit |
Delay time |
< 10 ms, On-delay
< 10 ms, Off-delay |
Efficiency |
98 % (η)
|
Input current ILN at 150% overload |
4.1 A
|
Leakage current at ground IPE - max |
3.5 mA
|
Mains current distortion |
120 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
480 V
|
Mains voltage tolerance |
380 - 480 V (-10 %/+10 %, at 50/60 Hz)
|
Operating mode |
Sensorless vector control (SLV)
Synchronous reluctance motors U/f control BLDC motors PM and LSPM motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Overload current |
At 40 °C
For 60 s every 600 s |
Overload current IL at 150% overload |
6.5 A
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) |
4.3 A at 150% overload (at an operating frequency of 8 kHz and an ambient air temperature of +40 °C)
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
1.5 kW
|
Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable, fPWM, Power section, Main circuit
|
System configuration type |
AC voltage
Center-point earthed star network (TN-S network) Phase-earthed AC supply systems are not permitted. |
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
2 HP
|
Braking current |
≤ 0.6 A (max. 6 A for 120 ms), Actuator for external motor brake
|
Braking torque |
Adjustable to 100 % (I/Ie), DC - Main circuit
|
Switch-on threshold for the braking transistor |
765 VDC
|
Rated conditional short-circuit current (Iq) |
10 kA
|
Short-circuit protection (external output circuits) |
Type 1 coordination via the power bus' feeder unit, Main circuit
|
Rated control voltage (Uc) |
24 V DC (-15 %/+20 %, external via AS-Interface® plug)
|
Communication interface |
AS-Interface
|
Connection |
Plug type: HAN Q4/2
|
Interfaces |
Max. total power consumption from AS-Interface® power supply unit (30 V): 190 mA
Number of slave addresses: 31 (AS-Interface®) Specification: S-7.4 (AS-Interface®) |
Cable length |
C2 ≤ 5 m, maximum motor cable length
C3 ≤ 25 m, maximum motor cable length C1 ≤ 1 m, maximum motor cable length |
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|